    Power Transmission and Distribution

    Gas-Insulated Switchgear

    up to 145 kV

    Type 8DN8

  • 7/30/2019 Siemens GIS

    2/18

    Benefitting from Experience

    2

    Durch die Feldteilung

    von nur 0,8 m wird

    der Raumbedarf un-

    serer 8DN8 auf ein

    Minimum reduziert

    The operator panel of

    the processor bus bay

    control system is inte-

    grated into the oper-

    ating front of the bay

    8DN8 switchgear

    for rated voltages

    up to 145 kV

    Both plug-in type and

    conventional cable

    sealing ends can be

    used in conjunction

    with type 8DN8

    switchgear

    Our 8D type range of gas-

    insulated switchgear represents

    a highly successful product

    concept. Since its introduction

    back in 1968, Siemens has

    installed more than 8000 bays

    worldwide. More than 100,000

    bay-years of operation have since

    been recorded.Intensive research work and

    continuous further development

    of the prototypes has ultimately

    led to todays generation of gas-

    insulated metal-enclosed

    switchgear. This switchgear is

    notable in particular for:

    Economic efficiency

    High reliability

    Safe encapsulation

    High degree of gas-tightness

    Minimal operating costs

    No maintenance Good accessibility

    High availability and

    Long service life.

    All requirements nowadays

    specified for modern and

    advanced switchgear in terms of

    performance and reliability are

    met by our type 8DN8

    switchgear for rated voltages of

    up to 145 kV. This switchgear

    design represents one of the most

    compact solutions available in this

    voltage range. Its space-savingdesign and its low weight

    contribute to making this

    switchgear extremely econom-

    ical. Since the levels of noise and

    field emission (EMC) are ex-

    tremely low, it is possible to

    integrate this switchgear even in

    sensitive environments,

    residential quarters and city

    centers.

    With these characteristics, our

    type 8DN8 switchgear meets all

    the requirements forenvironmentally compatible high-

    voltage switchgear.

  • 7/30/2019 Siemens GIS

    3/18

    3

  • 7/30/2019 Siemens GIS

    4/18

    1 Interrupter unit of the

    circuit-breaker

    2 Spring stored-energy

    mechanism with circuit-

    breaker control unit

    3 Busbar I with discon-

    nector and earthing

    switch4 Busbar II with discon-

    nector and earthing

    switch

    5 Outgoing feeder module

    with disconnector and

    earthing switch

    6 High-speed earthing

    switch

    7 Current transformer

    8 Voltage transformer

    9 Cable sealing end

    10 Integrated local control

    cubicle

    Three-phase enclosure

    allows compact design

    Efficient

    Due to Modular Design

    4

    M

    M

    x

    M

    M

    x

    M

    Temperature-related changes

    in the length of the enclosure

    and installation tolerances

    are compensated by bellows-

    type expansion joints. The

    conductors are linked by

    coupling contacts. Where

    necessary, the joints are

    accessible via manway open-

    ings. Gas-tight bushings allow

    subdivision of the bay into

    a number of separate gas

    compartments. Each gascompartment is provided with

    its own gas monitoring equip-

    ment, a rupture diaphragm

    and filter material. The static

    filters in the gas compart-

    ments absorb moisture and

    decomposition products.

    A fundamental feature of our

    gas-insulated switchgear is

    the high degree of versatility

    provided by its modular

    system. Depending on their

    respective functions, the

    components are housed

    either individually and/or

    combined in compressed-gas-

    tight enclosures. With a

    remarkably small number of

    active and passive modules,

    all customary circuit variantsare possible. Sulphur hexa-

    fluoride (SF6) is used as the

    insulating and arc-quenching

    medium.

    Three-phase enclosures are

    used for type 8DN8 switch-

    gear in order to achieve

    extremely low component

    dimensions. This concept

    allows a very compact design

    with reduced space require-

    ment. Aluminium is used for

    the enclosure. This assures

    freedom from corrosion and

    results in low weight of

    the equipment. Through the

    use of modern constructionmethods and casting tech-

    niques, it has been possible

    to optimize the dielectric and

    mechanical characteristics of

    the enclosure. The low bay

    weight ensures minimal floor

    loading and eliminates the

    need for complex foun-

    dations. All the modules are

    connected to one another by

    means of flanges. The gas-

    tightness of the flange con-

    nections is assured by provenO-ring seals.

    4

    7

    9

    8

    10

    5

    2

    3

    1

    6

    Gas-tight bushing

    Gas-permeable bushing

    The rupture diaphragms

    prevent build-up of an im-

    permissible high pressure in

    the enclosure. A gas diverter

    nozzle on the rupture dia-

    phragm ensures that the gas

    is expelled in a defined direc-

    tion in the event of bursting,

    thus ensuring that the oper-

    ating personnel is not

    endangered.

  • 7/30/2019 Siemens GIS

    5/18

    5

  • 7/30/2019 Siemens GIS

    6/18

    and compresses the re-

    maining arc-quenching gas.

    The compressed arc-quench-

    ing gas flows through the

    contact cylinder (5) into the

    contact gap and extinguishes

    the arc.

    Interruption of fault current

    If the short-circuit current is

    high, the arc-quenching gas

    at the arcing contact is heated

    up considerably by the energy

    of the arc. This leads to a

    pressure rise in the contact

    cylinder. Consequently, the

    energy required for produc-

    tion of the arc-quenching

    pressure does not have to be

    supplied by the operating

    mechanism. As the switching

    operation progresses, the

    fixed arcing contact releases

    the outflow from the nozzle

    (2). The gas now flows out

    of the contact cylinder and

    through the nozzle, thus ex-

    tinguishing the arc.

    Breaker in

    On position

    Breaking:

    Main contact

    open

    Arc-quenching principle

    6

    The central element of the

    gas-insulated switchgear is

    the three-pole circuit-breaker

    module enclosure comprising

    the following two main

    components:

    Interrupter unit

    Operating mechanism

    The design of the interrupter

    unit and of the operating

    mechanism is based on pro-

    ven and in most cases iden-

    tical designs, which have

    often been applied for

    outdoor switchgear

    installations.

    Circuit-breakermodule

    Interrupter unit

    The interrupter unit used in

    the circuit-breaker for arc-

    quenching operates on the

    self-compression principle.

    Owing to the low amount of

    drive energy required, the

    mechanical forces involved

    are minimal. This has a posi-tive effect on the stressing

    of both the circuit-breaker and

    the enclosure.

    1 Contact support

    2 Nozzle

    3 Main contact4 Arcing contact

    5 Contact cylinder

    6 Base

    1

    2

    3

    4

    5

    6

    The current path

    In the case of a self-compres-

    sion circuit-breaker, the

    current path is formed by the

    contact support (1), the base

    (6) and the moving contact

    cylinder (5). In the closedcondition, the operating

    current flows through the

    main contact (3). An arcing

    contact (4) is connected in

    parallel to the main contact.

    Interruption of

    operating current

    During the breaking

    operation, the main contact

    (3) opens first and the current

    commutates on the arcing

    contact (4), which is stillclosed. By this means, erosion

    of the main contact is

    avoided. As the breaking

    operation progresses, an arc

    develops between the

    contacts (4). The contact

    cylinder (5) moves

    simultaneously in the base (6)

    Circuit-breaker module

  • 7/30/2019 Siemens GIS

    7/18

    1 On release

    2 Cam disc

    3 Corner gears

    4 Drive linkage

    5 Connecting rod

    of the closing

    spring

    6 Connecting rod

    of the opening

    spring

    7 Closing spring

    8 Manual charging

    crank

    9 Charging

    mechanism

    10 Charging shaft

    11 Roller lever

    12 On damper

    13 Breaker actuatingshaft

    14 Off damper

    15 Off release

    16 Operating

    mechanism

    housing

    17 Opening spring

    Use is made of proven design

    principles of Siemens circuit-

    breakers, such as, for ex-

    ample, vibration-proof latches

    and load-free decoupling of

    the charging mechanism.

    The operating mechanism

    offers the following advan-

    tages: Defined switching position

    which is securely

    maintained even when the

    auxiliary power supply fails

    Tripping is possible irrespec-

    tive of the status of the clos-

    ing spring

    High number of mechanical

    operations

    Low number of mechanical

    parts

    Compact design.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    7

    Operating mechanism

    The spring stored-energy

    operating mechanism pro-

    vides the force for opening

    and closing the circuit-

    breaker. It is installed in a

    compact corrosion-free

    aluminium housing. The

    closing spring and theopening spring are arranged

    so as to ensure good visibility

    in the operating mechanism

    block. The entire operating

    mechanism unit is completely

    isolated from the SF6 gas

    compartments.

    Anti-friction bearings and a

    maintenance-free charging

    mechanism ensure many

    years of reliable operation.

    Breaking:

    Arcing contact

    open

    Breaker in

    Off position

  • 7/30/2019 Siemens GIS

    8/18

    Outgoing feeder module

    The outgoing feeder module

    connects the basic bay with

    various termination modules

    (for cable termination, over-

    head line termination and

    transformer termination).

    It contains a three-position

    switching device, whichcombines the functions of

    an outgoing feeder

    disconnector and of a bay-side

    earthing switch (work-in-

    progress type).

    Installation of a high-speed

    earthing switch and of a

    voltage transformer is also

    possible, where required. The

    high-voltage site testing

    equipment is generally

    connected to this module.

    Busbar module

    Connections between the

    bays are effected by means of

    busbars.

    The busbars of each bay are

    enclosed. Adjacent busbar

    modules are coupled by

    means of expansion joints.

    The module contains a three-position switching device,

    which combines the functions

    of a busbar disconnector and

    of a bay-side earthing switch

    (work-in-progress type).

    The moving contact either

    closes the isolating gap or

    connects the high-voltage

    conductor to the fixed contact

    of the earthing switch. Inte-

    gral mutual interlocking of the

    two functions is achieved as

    a result of this design, thus

    obviating the need for provi-sion of corresponding elec-

    trical interlocking within the

    switchgear bay. An insulated

    connection to the fixed con-

    tact of the earthing switch is

    provided outside the enclo-

    sure for test purposes.

    In the third neutral position

    neither the disconnector

    contact nor the earthing

    switch contact is closed.

    The three poles of a bay are

    mutually coupled and all the

    three poles are operated in

    common by a motor.

    Force is transmitted into the

    enclosure via gas-tight rotat-

    ing shaft glands. The check-

    back contacts and the on-off

    indicators are mechanically

    robust and are connected

    directly to the operating shaft.

    Emergency operation by hand

    is possible. The enclosure can

    be provided with inspection

    windows, in the case of which

    the On and Off position ofall three phases is visible.

    Neutral position

    Disconnector closed

    Earthing switch closed

    The functions of a disconnec-

    tor and of an earthing switch

    are combined in a three-

    position switching device.

    Busbar module

    Outgoing feeder module:

    Voltage transformer down-

    stream of the disconnector

    Outgoing feeder module:

    Voltage transformer

    upstream of the disconnector

    Three-position

    switching device

    Schematic diagram

  • 7/30/2019 Siemens GIS

    9/18

    Bus sectionalizers

    Bus sectionalizers are used for

    isolation of the busbar

    sections of a substation. They

    are integrated in the busbar

    in the same manner as a

    busbar module.

    The module contains a three-

    position switching device,which combines the functions

    of a bus sectionalizer and of

    an earthing switch (work-in-

    progress type).

    Voltage

    transformer module

    The voltage transformers

    operate on the principle of a

    voltage divider. Induction-

    type voltage transformers can

    be used as an alternative. The

    voltage transformers can be

    installed either upstream ordownstream of the outgoing

    feeder disconnector or at the

    busbar. The secondary-side

    connections are led out of the

    enclosure through a gas-tight

    bushing plate and are made

    available at terminals in the

    integrated local-control

    cubicle.

    Bus sectionalizer High-speed earthing switch

    9

    The high-speed earthing

    switch used is of the so-called

    pin-type. In this type of

    switch, the earthing pin at

    earth potential is pushed into

    the tulip-shaped fixed contact.

    The earthing switch is equipped

    with a spring-operated

    mechanism, charged by anelectric motor.

    Both current and voltage

    transformers are used for

    measuring and protection

    purposes. They are supplied

    in a number of variants

    ranging from conventional

    instrument transformers to

    advanced current and voltage

    sensors.

    Current

    transformer module

    As a general rule, power op-

    timized inductive-type current

    transformers are used. The

    current transformer can,

    however, be located at any

    point within the bay or sub-

    station. The high-voltage

    conductor, supported by gas-

    tight bushings, forms the

    primary winding. The coreswith the secondary windings

    are designed in line with the

    requirements in terms of class

    precision and rating.

    Changeover to a different

    transformation ratio is pos-

    sible by means of secondary-

    side connections of the

    current transformer, which

    are led out of the enclosure

    through gas-tight bushings

    and are made available at

    terminals in the integratedlocal-control cubicle.

    High-speed

    earthing switch

    Example: power-optimized

    voltage transformer module

    Example: power-optimized

    current transformer module

    Instrument

    transformers

  • 7/30/2019 Siemens GIS

    10/18

    Angular module

    Angular modules are used for

    splitting of the conductors

    in outgoing leads. They are

    available in designs with

    angles of 30, 45, 60 and

    90.

    T-module

    T-modules are used as

    branch-off point or for attach-

    ment of a surge arrester.

    They are available in various

    designs; however, their basic

    form is always identical.

    Extension module

    Single-poleextension module

    Three-poleextension module

    Three-pole 90angular module

    Design variants of single-pole angular modules

    Design variants of single-pole T-modules

    0

    Connection

    modules

    Splitting modules,

    single-pole/three-pole

    Splitting modules

    These modules are used to

    make the required joints

    within a bay and for pipework

    penetrations. Both single-pole

    and three-pole enclosed con-

    nection modules are available.

    The following connection

    modules can be used,

    depending on the circuit andthe spatial layout of the bay:

    The splitting modules are used

    for connection of three-pole

    plant components to single-

    pole components. As a rule,

    they serve as connections

    between the outgoing feeder

    module and various termi-

    nation modules (for overhead

    line termination, transformertermination).

  • 7/30/2019 Siemens GIS

    11/18

    The termination modules

    connect the bays of the gas-

    insulated switchgear to the

    following items of equipment:

    Overhead line

    Transformer or reactor coil

    Cable.

    They function as the transition

    link from the SF6 gas insula-

    tion within the enclosure to

    other insulating media.

    Cable termination module

    This three-pole module links

    the metal-enclosed gas-

    insulated switchgear with a

    high-voltage cable. All cus-

    tomary kinds of high-voltage

    cables can be connected. The

    primary conductor connection

    between the cable sealing endand the switchgear can be

    removed in the neighbouring

    outgoing feeder module in

    order to allow a high-voltage

    withstand test to be performed.

    Both conventional type cable

    sealing ends and plug-in types

    can be used.

    Outdoor

    termination module

    The single-pole outdoor ter-

    mination module forms the

    transition from the gas-

    insulated switchgear to air-

    insulated components or

    overhead lines. This termina-

    tion is a combination of asingle-pole connection

    module and an outdoor/SF6bushing. Length, shielding

    form and creepage distance

    of the outdoor/SF6 bushing

    are determined in line with

    insulation coordination, mini-

    mum clearance and degree of

    pollution. The outdoor

    termination module is suitable

    for air-insulated connections

    between GIS and:

    Overhead lines Outdoor bushings of out-

    door transformers or reactor

    coils

    Outdoor sealing ends of

    high-voltage cables.

    The splitting of the

    connection points for the

    three phases with the

    necessary clearance in air for

    conductor insulation is taken

    into account in the design of

    the switchgear.

    Transformer

    termination module

    The single-pole transformer

    termination module is con-

    nected (in a similar manner

    to the outdoor termination)

    to the three-pole enclosed

    basic bay via a combination

    of connection modules. It ef-fects the transition from the

    gas insulation directly to the

    bushing of oil-insulated

    transformers or reactor coils.

    The transformer bushing must

    be oil-tight and resistant to

    gas pressure.

    Temperature-related move-

    ments and non-uniform sett-

    ling by the foundations of

    switchgear and transformer

    are absorbed by expansion

    joints.

    11

    Termination

    modules

    Surge arrester

    module

    If required, enclosed surge

    arresters can be connected

    directly. They serve to limit

    the occurrence of overvolt-

    ages. Their active part con-

    sists of metal-oxide resistors

    with strongly non-linear

    current/voltage characteristics.

    The arrester is generallyflange-jointed to the switch-

    gear via a gas-tight bushing.

    The tank of the arrester

    module incorporates a man-

    way opening, through which

    the internal conductor can

    be accessed for inspection

    purposes. There are connec-

    tions for gas monitoring and

    arrester control devices on the

    underside.

    Example: Cable termination

    module (plug-in type)Surge arresterOutdoor termination module Transformer

    termination module

  • 7/30/2019 Siemens GIS

    12/18

    Proven and innovative switchgear control

    All the elements required for control and monitoring are accom-

    modated in a decentralized arrangement in the high-voltage

    switching devices. The switching device control systems are factory-

    tested and the switchgear is usually supplied with bay-internal

    cabling all the way to the integrated local control cubicle. This

    minimizes the time required for commissioning and reduces the

    scope for possible faults.

    As standard, the control and monitoring system is made up of

    electromechanical components.

    Alternatively, the digital intelligent control and protection system

    SICAM HV including comprehensive diagnostics and monitoring

    functions is available. More detailed information on the substation

    state means that maintenance intervals can be geared to the

    condition of the switchgear. Life-cycle costs can consequently be

    reduced even further.

    Operating mechanism

    cubicle of the circuit-

    breaker

    Gas monitoring

    Gas-tight insulating partitions divide each bay into functionally

    destinct gas compartments (circuit-breaker, disconnector, voltage

    transformer, etc.). The gas compartments are under constantobservation by means of density monitors with integrated indicator;

    any non-conformity is immediately signaled. The optionally available

    monitoring system with SICAM HV includes sensors that allow a

    trend forecast for each gas compartment.

    Flexible and reliable protection in bay and substation control

    Control and feeder protection are generally accommodated in the

    local control cubicle, which is itself integrated in the operating

    panel of the switchgear bay. This substantially reduces the amount

    of space required and also the time needed for commissioning.

    Alternatively, a version of the local control cubicle is available for

    installation separate from the switchgear. Various arrangements

    of the control and protection components are consequentlypossible. The cabling between the separately installed local control

    cubicle and the high-voltage switching devices is connected up

    via coded plugs, which minimize both the effort involved and the

    risk of errors.

    If requested, we can of course supply high-voltage switchgear

    featuring any customary bay and substation control equipment.

    We provide uniform systems to meet your individual requirements.

    Neutral interfaces in the switchgear control allow link-up of

    A conventional control system with contactor interlocking and

    control panel

    Digital control and protection comprising user-friendly bay con-

    trollers and substation automation with PC operator station (HMI) An intelligent, uniformly networked digital control and protection

    system with supplementary monitoring and telediagnostics

    functions.

    From the wide range of Siemens control and protection equipment,

    we can provide you a customized concept; everything comes from

    a single source.

    Integrated local control cubicle

    Control and Monitoring Uniform and Flexible Control and Protection

    2

  • 7/30/2019 Siemens GIS

    13/18

    To optimally facilitate

    transport and installation on

    site, our switchgear

    assemblies are shipped in

    units as large as possible, yet

    still easy to handle. It is thus

    possible to dispatch up to

    three completely assembled

    and tested switchgear bays,

    prefilled with SF6 gas, as a

    transport unit. In transport

    units containing switching

    devices, all operating

    mechanism attachments are

    preset in the factory prior to

    shipment. The jointing points

    of the transport units are

    protected against corrosion

    and are sealed with transportcovers. Goods are packed

    according to means, duration

    and route of transport, and

    also in line with nature and

    duration of storage.

    Shipments within Europe are

    normally transported by road.

    Switchgear supplied to

    countries outside Europe is

    enclosed in sealed packing,

    suitable for transport overseas

    and for a combined duration

    of transport and storage of upto 12 months. In special cases,

    the sealed packing can also

    be designed for a longer

    period.

    The delivery of complete

    factory-assembled bays

    significantly reduces the effort

    required for installation on

    site. The transport unit is

    brought to its place of in-

    stallation by means of simple

    equipment and is aligned

    ready for assembly with the

    other bays. A mounting frame

    facilitates movement and

    rapid alignment of the bays.

    Only a limited number of

    anchorings and additional

    steel supports is required for

    securing the switchgear to the

    foundation. Depending on the

    bay design, only the bay

    termination needs to beassembled. Only bay-to-bay

    cabling has to be installed on

    the secondary side.

    Uncomplicated work proce-

    dures, detailed installation

    instructions and the use of

    relatively few special tools

    allow easy and rapid installa-

    tion of the switchgear by your

    own personnel under the

    guidance of an experienced

    supervisor from Siemens. Our

    training facilities are at yourdisposal.

    When the assembly work has

    been completed, all switching

    devices and all electrical cir-

    cuits for control and moni-

    toring are tested to ensure

    that they function properly in

    both mechanical and electrical

    terms. Flange joints made on

    site are tested for gas leaks.

    All other flange joints are al-

    ready factory-tested.

    All tests are performed in

    conformity with IEC. The

    results are documented in

    reports.

    Our gas-insulated switchgear

    is designed and manufactured

    so as to produce an optimal

    balance between design, ma-

    terials used and maintenance

    required.

    The hermetically-sealed en-

    closures and automatic moni-

    toring ensure minimal switch-

    gear maintenance; under

    normal operating conditions

    the assemblies are practically

    maintenance-free. We recom-

    mend that the first major in-

    spection be carried out after

    25 years.

    Transport, Installation,

    Commissioning, Maintenance

    Transport Commissioning Maintenance

    13

    Installation

    and erection

    High-voltage test on site

    Factory-assembled panel

  • 7/30/2019 Siemens GIS

    14/18

    The quality of Siemens

    gas-insulated switchgear is

    assured by an all-encompas-

    sing, state-of-the-art quality-

    management system. The

    system was certified in 1983

    in accordance with CSA Z299

    and again in 1989 in accord-ance with DIN EN ISO 9001.

    Quality assurance for us is

    primarily a means to increase

    the customer orientation of

    our activities.

    The quality assurance system

    comprises all product life-

    cycle sequences, ranging from

    marketing to after-sales

    service. Regular management

    reviews, internal audits and

    external audits of all proces-

    ses ensure that the system iseffective and up-to-date.

    Documentation of all quality-

    relevant sequences forms

    the basis. The quality of our

    switchgear consequently

    meets even the highest

    requirements.

    Consistent quality manage-

    ment naturally also extends

    to the production of our gas-

    insulated switchgear. As-

    sembly under clean-room

    conditions, comprehensivemanufacturing inspections

    and routine tests on individual

    components and complete

    modules assure reliable

    switchgear operation. Follow-

    ing mechanical routine tests,

    the final quality verification

    takes place in the form of a

    high-voltage test on the

    complete bay (or on the

    transport units) prior to ship-

    ment.

    Quality Assurance

    4

  • 7/30/2019 Siemens GIS

    15/18

    All the standard circuit con-

    figurations can be realized

    using our type 8DN8 switch-gear.

    2850

    3300

    Bay weight approx. 2.8 t

    Coupling bay

    5

    Typical

    Bay Arrangement

    H-configurationDuplicate busbar system

    6400

    3500

    3500

    M

    MMMM

    M

    M

    M

    M MM

    M

    MM

    M

    M M MM M M

    M

    MM

    M

    MM

    M

    M

    M

    H-Configuration

  • 7/30/2019 Siemens GIS

    16/18

    3500

    3100

    2850

    3500

    Bay weight approx. 3.1 t Bay weight approx. 3 t

    H-configurationOverhead line bay

    16

    Direct connection to the transformer

    6700 3500

    3100

    Bay weight approx. 3.1 t

    M

    M

    M MM

    M

  • 7/30/2019 Siemens GIS

    17/18

    Technical

    Data

    17

    Switchgear type 8DN8

    Rated voltage up to 145 kV

    Rated frequency 50/60 Hz

    Rated power frequency up to 275 kVwithstand voltage (1 min)

    Rated lightning impulse up to 650 kV

    withstand voltage (1.2/50 s)

    Rated busbar current up to 3150 A

    Rated feeder current up to 3150 A

    Rated breaking current up to 40 kA

    Rated impulse current up to 108 kA

    Rated short-time current up to 40 kA

    Leakage rate per year and gas 0,5 %

    compartment

    Bay width 800 mm

    Height, depth

    Standards EN/IEC

    see typical

    bay arrange-

    ments

  • 7/30/2019 Siemens GIS

    18/18

    Tel.: +49 180 / 524 70 00

    Fax: +49 180 / 524 24 71

    E-mail: [email protected]

    www.siemens.com/ptd-support

    (Subject to changee.g. 12 ct/min)

    For further questions about our Power

    Transmission and Distribution offers please contact

    our Customer Support Center 24/7 at:

    The information in this document contains generaldescriptions of the technical options available, whichdo not always have to be present in individual cases.The required features should therefore be specifiedin each individual case at the time of closing the

    contract.

    Siemens AG

    Power Transmission

    and Distribution

    High Voltage DivisionPostfach 32 20

    91050 Erlangen

    Germany

    www.siemens.com/ptd

    Subject to change without prior notice

    Order No. E50001-U113-A179-V2-7600

    Printed in Germany

    Dispo-Stelle 30000

    61D7228 TV/EK100828 PA1003.

    Further copies of this brochure

    HIS Highly-integrated switchgear up to 145 kV

    HIS Highly-integrated switchgear up to 550 kV

    HIS CD-ROM for Windows 95/NT 4.0 or higherGas-insulated switchgear up to 245 kV

    Gas-insulated switchgear up to 300 kV

    Gas-insulated switchgear up to 550 kV

    Container-type switchgear

    Digital control and monitoring for high-voltage switching devices

    Gas-insulated switchgear product range