emtp user group092008 sadovic etudes web
TRANSCRIPT
![Page 1: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/1.jpg)
ETUDES DE COORDINATION D’ISOLEMENT
S. Sadovic, T. Sadovicwww.sadovic.com
Clamart, 25.09.2008
Journée Club des Utilisateurs EMTP-RV
![Page 2: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/2.jpg)
ETUDE TYPE DE COORDINATION D’ISOLEMENT
UTILISANT EMTP-RV
1. PROTECTION CONTRE LA FOUDRE DES STATIONS A HAUTE TENSION
2. PERFORMANCE DE LIGNE DE TRANSMISSION FACE A LA FOUDRE
3. SURTENSION DE MANOEUVRE
![Page 3: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/3.jpg)
Coup de foudre généré –défaut de câble de garde
PB
Parafoudre
Modèle de câble FD
Poste Blindé connecté par câble 132 kV
![Page 4: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/4.jpg)
Poste Blindé connecté par câble 132 kV
EMTP exécuté en boucle
Les longueurs des câbles sont automatiquement changées (12 valeurs)
Les résultats sont automatiquement extraits des fichiers de sortie EMTP
![Page 5: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/5.jpg)
Poste Blindé connecté par câble 132 kV – Surtension au transformateur
![Page 6: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/6.jpg)
7
1
2
3
4
5
6
8
Option OHGW
Option TLSA
LSA
Amélioration des performance des lignes façe à la foudreLIGNE DOUBLE TERNE 69 kV CdG ou PdL
Utilisant EMTP pour la computation
Line general data:
Un = 69 kV - Line nominal voltage
l = 100 km- Line total lengthlS = 150 m - Line span (average)
LSA: Line Surge ArresterTd = 12 (thunder days)
Conductor data: No x (m) y(m) r (mm) sag (m)
1 (top left) -3,5 20 9 4 2 (middle left) -3,5 17 9 4 3 (bottom left) -3,5 14 9 4 4 (top right) 3,5 20 9 4 5 (middle right) 3,5 17 9 4 6 (bottom right) 3,5 14 9 4 7 (ground wire) -2 22,6 5 3 8 (ground wire) 2 22,6 5 3
![Page 7: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/7.jpg)
LIGNE DOUBLE TERNE 69 kVCdG ou PdL
Données du Parafoudre de Ligne:
- Duty cycle voltage: 66 kVrms
- MCOV: 52 kVrm
- IEC Line discharge class: 2
- Nominal discharge current: 10 kApeak
- High current withstand strength: 100 kApeak
![Page 8: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/8.jpg)
LIGNE DOUBLE TERNE 69 kVCdG ou PdL
CFO (U50%)
(kV) TOTAL
Flashover Rate [fls/100km/y]
DOUBLE CIRCUIT Flashover Rate [fls/100km/y]
350 1,42 0,59 400 0,91 0,23 450 0,57 0,13 500 0,31 0,06
CFO (U50%)
(kV) TOTAL
Flashover Rate [fls/100km/y]
DOUBLE CIRCUIT Flashover Rate [fls/100km/y]
350 2,27 1,30 400 1,49 0,89 450 1,21 0,66 500 0,91 0,37
2 CdG
2 PdL
![Page 9: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/9.jpg)
Ligne double terne compacte 138 kV sans câble de garde
Taux d’amorçage total [Ng = 8,09 coups/km2/an]
0
10
20
30
40
50
60
70
80
90
100
10 20 30 40 50 60 70 80 90 100
Tower Footing Resistance (ohm)
Flsh
/100
km/y
ear
LSA 0 LSA 1,4 LSA 1,3,4 LSA 1,3,4,6
LSA
12,3 m
3,6 m
COMPACT
2 m
![Page 10: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/10.jpg)
Ligne double terne compacte 138 kV sans câble de garde
Taux d’amorçage double terne [Ng = 8,09 coups/km2/an]
LSA
12,3 m
3,6 m
COMPACT
2 m
0
5
10
15
20
25
30
10 20 30 40 50 60 70 80 90 100
Tower Footing Resistance (ohm)
Flsh
/100
km/y
ear
LSA 0 LSA 1,4 LSA 1,3,4 LSA 1,3,4,6
![Page 11: Emtp User Group092008 Sadovic Etudes Web](https://reader038.vdocuments.fr/reader038/viewer/2022100518/559ba1b31a28abfa148b4614/html5/thumbnails/11.jpg)
Ligne 400 kV – Contrôle des surtensions de manoeuvreUtilisant EMTP pour la computation