Smoke evacuation shutter (remote-controlled)
Avantage
V1
3-C
02
/20
13
NF-Clapets coupe-feu etVolets de désenfumage D.A.S.
NF 264www.marque-nf.com
1812
Avantage Smoke evacuation shutter (remote-controlled)V13-C
02/2013
2
Content
Content • ProduCt Presentation • range .....................................................................................................................2 Fire resistanCe • aPProvals and test rePorts • oPtions .............................................................................................3 storage and handling • dimensions and installation. ................................................................................................ .4 eleCtriCal ConneCtions .......................................................................................................................................................6 oPerating ...............................................................................................................................................................................7 maintenanCe • evolution - kits ........................................................................................................................................8 teChniCal data ......................................................................................................................................................................9 Free air Passage...................................................................................................................................................................10 samPle order .......................................................................................................................................................................11
ProduCt Presentation
Avantage smoke evacuation shutters are noted for their superior airtight properties. Avantage smoke evacuation shutters offer a fire-resistance of 60 to 120 minutes, and ensure minimum pressure loss. They were developed in accordance with the European product standard EN 12101-8 and tested according to the EN 1366-10 standard. The shutter Avantage 1V is available in motorised model (ME). Smoke evacuation shutters are meant for the evacuation of smoke in a number of buildings, depending on local legislation (apartment buildings, public-access buildings (PAB), tall buildings, etc.) • Tested according to EN 1366-10, product conform to norm EN 12101-8 and NF S 61937-10 • Superior air tightness • Minimal pressure drop • Suitable for mounting in calcium-silicate duct and staff • Easy to install • Maintenance free • For indoor applications
range
Minimal dimensions W x H [mm] Maximal dimensions W x H [mm]1V 60 1V 120 300x385 700x1075
2V 60 2V 120 350x385 1100 x1105
1V 60 ME 2V 120 ME 350x385 700x1075
W= WidthH= Height
See complete range p. 10-11
1. 1 shutter (1V) / 2 shutters (2V) 2. Aluminium frame 3. Lock + key 4. Connection compartment5. Blocking mechanism6. Central support 7. Product marking 8.Rearmation motor
5
8
4
5
4 21 73
6
Avantage 1V Avantage 2V Avantage 1V ME
5
Smoke evacuation shutter (remote-controlled)V13-C
02/2013
3
Avantage
Fire resistanCe aCCording to en 13501-4
thickness plates
Avantage 1V (ME)/2V 60 Avantage 1V (ME)/2V 120
Mounting in calcium-silicate duct30 mm EI 60 (ved-i↔o)
S1500AAmulti -
50 mm EI 60 (ved-i↔o) S1500AAmulti
EI 120 (ved-i↔o) S1500AAmulti
Mounting in staff duct30 mm EI 60 (ved-i↔o)
S1500AAmulti -
45 mm EI 60 (ved-i↔o) S1500AAmulti
EI 120 (ved-i↔o) S1500AAmulti
E = integrity 60/120 = fire resistance i↔o = fire side randomly I = thermal insulation ved = vertical duct AA = automatic activation S = smoke leakage 1500 = pression level 3 multi = multiple compartment
aPProvals and test rePorts
All our shutters are submitted to tests by official test institutes. Reports of these tests form the basis for the approvals of our dampers
1812 Europe : Classification following EN 12101-8 (Certificat 1812-CPD-1042) France : NF certificat : 05,25 (1V) and 05,26 (2V)
ISO : Certification: ISO 9001
oPtions
1. Bipolar beginning and end of range switch FDCB
2. Mounting frame KAP 3. Technical front protection grill GFV-PB
2 bipolar beginning and end of range switches (FDCB), FDCU standard included
Build in mounting frame for all wall types (delivered separately)
Steel frame with grill in perforated steel plate (delivered separately)
iCaution:• Using a mounting frame has an impact on the dimensions of the opening.
4
Avantage Smoke evacuation shutter (remote-controlled)V13-C
02/2013
4
storage and handling
As the smoke evacuation shutter is a safety element it needs to be stored and handled with caution. iCaution:
• store in a building away from humidity• avoid any kind of damage• avoid contact with water It is recommended: • to unload in a dry area • to avoid shocks • not to rotate the smoke shutter while moving it • not to use the shutter as a scaffold, working table, etc.• not to store smaller shutters inside larger ones
dimensions and installation
Wn Wn + 10
Wn + 54
(1V
) W
n +
52
(2V
) W
n/2
+ 6
6
min
.105
10
Wn + 20
2
1
3
iCaution :
• When fitting, the shutter should be protected from any sealing products and handled with care. • Before putting the installation into operation, clean off all the dust and dirt. • If fitting in a smoke evacuation duct, bear in mind the shutter's clearance.
Legend :
1. Refractory material (ex. calcium-silicate plate) 2. Sealing (ex. plaster) if mounting frame is used 3. KAP mounting frame (option)
5
Smoke evacuation shutter (remote-controlled)Avantage V13-C02/2013
Application to other duct constructions than those used during the test:
Multi- compartment smoke control dampers may be applied to ducts that have been tested to EN 1366-9 and EN 1366-8 as appropriate, constructed from materials of the same density as those tested or of the same material with a greater density or thickness.
The duct should be built according to the manufacturer's classification report.
Installation in calcium-silicate or staff duct
Fixation with mounting frame Fixation by direct sealing
Reference / RéférencePlate / Planche
Plan Title / Titre du planD
ate / Date:
23/08/2011
3/3Subject / Sujet
Notice V
A-1V
NT-V
A-1V
-2-Montage
(L +
A) x
(H+
A) m
m
e
e
Reference / RéférencePlate / Planche
Plan Title / Titre du planD
ate / Date:
23/08/2011
2/2Subject / Sujet
Notice V
A-1V
NT-V
A-1V
-3-Montage
(L +
A) x
(H+
A) m
m
e
e
1. Make an opening of (W + A) x (H + A)mm (A = 2x(thickness of sleeve e)+20).
2. Fit a sleeve (thickness e) of 105mm deep in the opening.3. Fix the sleeve to the partition wall.4. Seal the mounting frame taking care not to misshape it. 2
sealing lugs are provided on each fitting, which must be opened out when sealing. The finished opening must be the same size as the mounting frame (W + 10) x (H + 10)mm.
5. Position the shutter in the mounting frame and fix the shutter to the frame using 4 screws M6, supplied with the frame.
iCaution : make sure that the screws don't exceed the thickness of the sleeve !
1. Make an opening of (W + A) x (H + A)mm (A = 2x(thickness of sleeve e)+10).
2. Fit a sleeve (thickness e) of 105mm deep in the opening.3. Fix the sleeve to the partition wall.4. Position the shutter in the mounting frame and fix the
shutter to the frame using 4 screws M6, supplied with the frame.
iCaution : make sure that the screws don't exceed the thickness of the sleeve !
6
Smoke evacuation shutter (remote-controlled)Avantage V13-C 02/2013
eleCtriCal ConneCtions
Wiring diagram
Avantage: Avantage 1V ME:
FCU
121110
DCB
NONFC
15 161413
FCB
NONFC
9875 6
DCU
NONFCNONFC
1
-+
2
24/48 V DC +/- 10%24/48 V AC +/- 10%
24 V DC 48 V DC
FCU
121110
DCB
NONFC
15 161413
FCB
NONFC
9875 6
DCU
NONFCNONFC
ME
4
+ - + -
321
24/48 V DC
24 V DC 48 V DC
Technical data
Power supply Position switches
Magnet: 24VDC or 48VDC Standard: 1mA...6A, DC 5V...AC 250V
Motor: dual voltage 24/48 VDC
Power consumption Degree of protection
Magnet VD: Pmax = 3,5W IP 42
VM: Pnom = 1,5W
Motor 24V: Pmax= 20W
48V: Pmax= 50W
Explanation of the abbreviations
VAC= Alternative current V= Volt PMAx
= Maximal capacity MOD= ModuleVCC= Direct current W= Watt P
NOM= Nominal capacity DAS MOD=Modular product
E.ALIM= Power input TELE= Remote controlled S.L.= Free surface E.TELE= Entry control
Electrical incoming feeder DETAIL A SCALE 1 : 5
Reference / Référence Plate / Planche
Plan Title / Titre du plan Date / Date:
24/08/2011
1/1Subject / Sujet
Notice VA-1V
NT-VA-1V-Arrivée électrique
The electrical supply can be done at the 4 corners of the shutter.
It is enough to drill a hole in the refractory at the side needed, the galvanised part is already indented.
Connection cables can be fixed with fixation clips, present in the connection box.
Finally, install, between the electrical supply and the connection box, the cable-tie that prevents from unintentionally pulling the cables (included in the connection box). Comply with the installation rules according to article 6.1 of NF S 61-932
7
Smoke evacuation shutter (remote-controlled)Avantage V13-C02/2013
oPerating avantage
iCaution : Please note that the shutters are not allowed to open when the ventilators are working.
1V
Manual / remote control (opening) Manual rearmation (closing)
20°
20°
Manual1. Insert the key in the lock2. Turn the key 20° counter clock wise: the shutter opens3. Withdraw the key
RemoteBy sending an electrical impulse (VD) or by interrupting (VM) the power supply to the magnet
1. Push the blocking mechanism2. Close the shutter by pulling at the central profile
1V ME
Manual / remote control (opening) Manual / remote control (closing)
20°
20°
Manual
1. Insert the key in the lock2. Turn the key 20° counter clock wise: the shutter opens3. Withdraw the keyRemote By sending an electrical impulse (VD) or by interrupting (VM) the power supply to the magnet
Manual
1. Push the blocking mechanism2. Close the shutter by pulling at the central profileRemote
1. Supply the actuator for at least 90sec. (respect the prescribed voltage). 3. The rearmation stops automatically when the shutter is closed! Switch off the power supply after rearmation ! Switch off the power supply for at least 90 sec. in between each rearmation cycle.
eleCtriCal ConneCtions
Wiring diagram
Avantage: Avantage 1V ME:
FCU
121110
DCB
NONFC
15 161413
FCB
NONFC
9875 6
DCU
NONFCNONFC
1
-+
2
24/48 V DC +/- 10%24/48 V AC +/- 10%
24 V DC 48 V DC
FCU
121110
DCB
NONFC
15 161413
FCB
NONFC
9875 6
DCU
NONFCNONFC
ME
4
+ - + -
321
24/48 V DC
24 V DC 48 V DC
Technical data
Power supply Position switches
Magnet: 24VDC or 48VDC Standard: 1mA...6A, DC 5V...AC 250V
Motor: dual voltage 24/48 VDC
Power consumption Degree of protection
Magnet VD: Pmax = 3,5W IP 42
VM: Pnom = 1,5W
Motor 24V: Pmax= 20W
48V: Pmax= 50W
Explanation of the abbreviations
VAC= Alternative current V= Volt PMAx
= Maximal capacity MOD= ModuleVCC= Direct current W= Watt P
NOM= Nominal capacity DAS MOD=Modular product
E.ALIM= Power input TELE= Remote controlled S.L.= Free surface E.TELE= Entry control
Electrical incoming feeder DETAIL A SCALE 1 : 5
Reference / Référence Plate / Planche
Plan Title / Titre du plan Date / Date:
24/08/2011
1/1Subject / Sujet
Notice VA-1V
NT-VA-1V-Arrivée électrique
The electrical supply can be done at the 4 corners of the shutter.
It is enough to drill a hole in the refractory at the side needed, the galvanised part is already indented.
Connection cables can be fixed with fixation clips, present in the connection box.
Finally, install, between the electrical supply and the connection box, the cable-tie that prevents from unintentionally pulling the cables (included in the connection box). Comply with the installation rules according to article 6.1 of NF S 61-932
8
Smoke evacuation shutter (remote-controlled)Avantage V13-C 02/2013
2V
Manual/remote control (opening) Manual rearmation (closing)
20°
20°
A
B
12
Manual1. Insert the key in the lock2. Turn the key 20° counter clock wise: the shutter opens3. Withdraw the key
RemoteBy sending an electrical impulse (VD) or by interrupting (VM) the power supply to the magnet
1. Push the blocking mechanism of the first shutter 2. Close the shutter by pulling at the central profile 3. Push the blocking mechanism of the second shutter 4. Close the shutter by pulling at the central profile and hold the door in your hand (A) 5. Open the first shutter with the key until position B. 6. Close both shutters together 7. Withdraw the key
maintenanCe - No specific maintenance required - Schedule at least two running checks each year - Remove dust and all other particles before start-up - Respect the maintenance regulations according to NF S 61-933 or to local provisions evolution kits
KIT VD24 VA (MOD) KIT VD48 VA (MOD)
Magnet VD24/48
KIT VM24 VA (MOD) KIT VM48 VA (MOD)
Magnet VM24/48
KIT FDC VA (MOD)
2 beginning and end of range switches FDCB
KIT ME-AVANM
Dual voltage rearmation motor ME 24VDC-48VDC for Avantage 1V ME
9
Smoke evacuation shutter (remote-controlled)Avantage V13-C02/2013
teChniCal data
Collective duct Shunt or single duct
Product Smoke evacuation shutter Smoke evacuation shutter
Certification
1812 1812
Obligation Rearmation possible after cold unlocking Beginning of range position switch (DCU) End of range position switch (FCU)
Rearmation possible after cold unlocking Manual control integrated on level 0 or 1 on opening
Security options Manual control integrated on level 1 for opening and closing
Beginning of range position switch (DCU) End of range position switch (FCU)
Interdiction Change of state prohibited after interrupting of power supply to the magnet
Functioning Without external energy Without external energy
Operation Remote controlled by sending an electrical impulse (VD) to the magnet
Remote controlled by sending an electrical impulse (VD) or by interrupting (VM) the power supply to the magnet
Power supply 24 or 48 Vdc 24 or 48 Vdc
Power consumption 3.5W by electrical impulse (VD) 3.5W by electrical impulse (VD) 1.5W by interrupting (VM) the power supply
Installation direction Axis of the damper blade vertical Axis of the damper blade vertical
Additional Function Bipolar position switch FCB/DCB For 1V ME: rearmation motor ME
Bipolar position switch FCB/DCB For 1V ME: rearmation motor ME
Direction of air circulation
Random Random
Free air passage 1V ((L-56)x(H-56)-4000)/10.000
2V ((L-56)x(H-56)-4000)x(29.2x(H-56)))/10.000
Dimensions WxH See pages 10-12
Durability test After 300 cycles the characteristics stay within declared limit values.
Fire resistance classification
Classification Fire resistance (1500 AA multi):- EI 120 (ved-i o) S 1500 AA multi : range 1V/2V 120: Installation in staff duct 45mm - EI 120 (ved-i o) S 1500 AA multi : range 1V/2V 120: Installation in calcium-silicate duct 50mm - EI 60 (ved-i o) S 1500 AA multi : range 1V/2V 60: Installation in staff duct 30mm - EI 60 (ved-i o) S 1500 AA multi : range 1V/2V 60: Installation in calcium-silicate duct 30mm
Fire side Random Random
Mounting In wall Fixation with or without mounting frame
In wall Fixation with or without mounting frame
Grill With finishing grill With finishing grill
Kits Yes Yes
List of kits See page 8 See page 8
Certifying organization: AFNOR Certification 11 Rue Francis de Pressensé F93571 La Plaine Saint-Denis Cedex
The NF-label guarantees: - The conformity with the standard NF S 61-937 Parts 1 & 5: “Systèmes de Sécurité Incendie Dispositifs Actionnés de Sécurité” - The conformity with the national decree of march 22, 2004 - The values of the characteristics mentioned in this document
10
Smoke evacuation shutter (remote-controlled)Avantage V13-C 02/2013
Free air Passage
iFind the complete selection data and select the ideal product on www.logi-k.fr
Free air passage Avantage 1V
H\W [mm] 300 350 400 450 500 550 600 650 700
385 7,6 9,3 10,9 12,6 14,2 15,9 17,5 19,1 20,8
415 8,4 10,2 11,9 13,7 15,5 17,3 19,1 20,9 22,7
445 9,1 11,0 13,0 14,9 16,9 18,8 20,8 22,7 24,7
475 9,8 11,9 14,0 16,1 18,2 20,3 22,4 24,5 26,6
505 10,6 12,8 15,0 17,3 19,5 21,8 24,0 26,3 28,5
535 11,3 13,7 16,1 18,5 20,9 23,3 25,7 28,1 30,4
565 12,0 14,6 17,1 19,7 22,2 24,7 27,3 29,8 32,4
595 12,8 15,4 18,1 20,8 23,5 26,2 28,9 31,6 34,3
625 13,5 16,3 19,2 22,0 24,9 27,7 30,6 33,4 36,2
655 14,2 17,2 20,2 23,2 26,2 29,2 32,2 35,2 38,2
685 14,9 18,1 21,2 24,4 27,5 30,7 33,8 37,0 40,1
715 15,7 19,0 22,3 25,6 28,9 32,2 35,4 38,7 42,0
745 16,4 19,9 23,3 26,7 30,2 33,6 37,1 40,5 44,0
775 17,1 20,7 24,3 27,9 31,5 35,1 38,7 42,3 45,9
805 17,9 21,6 25,4 29,1 32,9 36,6 40,3 44,1 47,8
835 18,6 22,5 26,4 30,3 34,2 38,1 42,0 45,9 49,8
865 19,3 23,4 27,4 31,5 35,5 39,6 43,6 47,7 51,7
895 20,1 24,3 28,5 32,7 36,9 41,0 45,2 49,4 53,6
925 20,8 25,1 29,5 33,8 38,2 42,5 46,9 51,2 55,6
955 21,5 26,0 30,5 35,0 39,5 44,0 48,5 53,0 57,5
985 22,3 26,9 31,6 36,2 40,8 45,5 50,1 54,8 59,4
1015 23,0 27,8 32,6 37,4 42,2 47,0 51,8 56,6 61,4
1045 23,7 28,7 33,6 38,6 43,5 48,5 53,4 58,3 63,3
1075 24,5 29,6 34,7 39,7 44,8 49,9 55,0 60,1 65,2
11
Smoke evacuation shutter (remote-controlled)Avantage V13-C02/2013
Section nette de passage Avantage 1V ME
H\L [mm] 350 400 450 500 550 600 650 700
385 8,6 10,2 11,8 13,4 15,1 16,7 18,3 19,9
415 9,5 11,2 13,0 14,8 16,5 18,3 20,1 21,8
445 10,3 12,3 14,2 16,1 18,0 19,9 21,8 23,8
475 11,2 13,3 15,4 17,4 19,5 21,6 23,6 25,7
505 12,1 14,3 16,6 18,8 21,0 23,2 25,4 27,6
535 13,0 15,4 17,7 20,1 22,5 24,8 27,2 29,6
565 13,9 16,4 18,9 21,4 23,9 26,5 29,0 31,5
595 14,8 17,4 20,1 22,8 25,4 28,1 30,8 33,4
625 15,6 18,5 21,3 24,1 26,9 29,7 32,5 35,4
655 16,5 19,5 22,5 25,4 28,4 31,4 34,3 37,3
685 17,4 20,5 23,6 26,8 29,9 33,0 36,1 39,2
715 18,3 21,5 24,8 28,1 31,4 34,6 37,9 41,1
745 19,2 22,6 26,0 29,4 32,8 36,3 39,7 43,1
775 20,0 23,6 27,2 30,8 34,3 37,9 41,4 45,0
805 20,9 24,6 28,4 32,1 35,8 39,5 43,2 46,9
835 21,8 25,7 29,6 33,4 37,3 41,1 45,0 48,9
865 22,7 26,7 30,7 34,7 38,8 42,8 46,8 50,8
895 23,6 27,7 31,9 36,1 40,2 44,4 48,6 52,7
925 24,5 28,8 33,1 37,4 41,7 46,0 50,4 54,7
955 25,3 29,8 34,3 38,7 43,2 47,7 52,1 56,6
985 26,2 30,8 35,5 40,1 44,7 49,3 53,9 58,5
1015 27,1 31,9 36,6 41,4 46,2 50,9 55,7 60,5
1045 28,0 32,9 37,8 42,7 47,7 52,6 57,5 62,4
1075 28,9 33,9 39,0 44,1 49,1 54,2 59,3 64,3
12
Smoke evacuation shutter (remote-controlled)Avantage V13-C 02/2013
Free air passage Avantage 2V
H\W[mm] 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100
385 8,3 10,0 11,6 13,2 14,9 16,5 18,2 19,8 21,5 23,1 24,8 26,4 28,1 29,7 31,3 33,0
415 9,1 10,9 12,7 14,5 16,3 18,1 19,9 21,7 23,5 25,3 27,1 28,9 30,6 32,4 34,2 36,0
445 9,9 11,8 13,8 15,7 17,7 19,6 21,6 23,5 25,5 27,4 29,4 31,3 33,2 35,2 37,1 39,1
475 10,7 12,8 14,9 17,0 19,1 21,2 23,3 25,4 27,5 29,6 31,6 33,7 35,8 37,9 40,0 42,1
505 11,5 13,7 16,0 18,2 20,5 22,7 25,0 27,2 29,4 31,7 33,9 36,2 38,4 40,7 42,9 45,2
535 12,3 14,7 17,1 19,5 21,9 24,3 26,7 29,0 31,4 33,8 36,2 38,6 41,0 43,4 45,8 48,2
565 13,1 15,6 18,2 20,7 23,3 25,8 28,3 30,9 33,4 36,0 38,5 41,1 43,6 46,2 48,7 51,3
595 13,9 16,6 19,3 22,0 24,7 27,3 30,0 32,7 35,4 38,1 40,8 43,5 46,2 48,9 51,6 54,3
625 14,7 17,5 20,4 23,2 26,0 28,9 31,7 34,6 37,4 40,3 43,1 46,0 48,8 51,7 54,5 57,3
655 15,5 18,5 21,5 24,4 27,4 30,4 33,4 36,4 39,4 42,4 45,4 48,4 51,4 54,4 57,4 60,4
685 16,3 19,4 22,5 25,7 28,8 32,0 35,1 38,3 41,4 44,6 47,7 50,9 54,0 57,1 60,3 63,4
715 17,1 20,3 23,6 26,9 30,2 33,5 36,8 40,1 43,4 46,7 50,0 53,3 56,6 59,9 63,2 66,5
745 17,8 21,3 24,7 28,2 31,6 35,1 38,5 42,0 45,4 48,8 52,3 55,7 59,2 62,6 66,1 69,5
775 18,6 22,2 25,8 29,4 33,0 36,6 40,2 43,8 47,4 51,0 54,6 58,2 61,8 65,4 69,0 72,6
805 19,4 23,2 26,9 30,7 34,4 38,2 41,9 45,6 49,4 53,1 56,9 60,6 64,4 68,1 71,9 75,6
835 20,2 24,1 28,0 31,9 35,8 39,7 43,6 47,5 51,4 55,3 59,2 63,1 67,0 70,9 74,8 78,7
865 21,0 25,1 29,1 33,2 37,2 41,2 45,3 49,3 53,4 57,4 61,5 65,5 69,6 73,6 77,7 81,7
895 21,8 26,0 30,2 34,4 38,6 42,8 47,0 51,2 55,4 59,6 63,8 68,0 72,2 76,4 80,5 84,7
925 22,6 27,0 31,3 35,6 40,0 44,3 48,7 53,0 57,4 61,7 66,1 70,4 74,8 79,1 83,4 87,8
955 23,4 27,9 32,4 36,9 41,4 45,9 50,4 54,9 59,4 63,9 68,4 72,9 77,3 81,8 86,3 90,8
985 24,2 28,8 33,5 38,1 42,8 47,4 52,1 56,7 61,4 66,0 70,6 75,3 79,9 84,6 89,2 93,9
1015 25,0 29,8 34,6 39,4 44,2 49,0 53,8 58,6 63,4 68,1 72,9 77,7 82,5 87,3 92,1 96,9
1045 25,8 30,7 35,7 40,6 45,6 50,5 55,5 60,4 65,3 70,3 75,2 80,2 85,1 90,1 95,0 100,0
1075 26,6 31,7 36,8 41,9 47,0 52,1 57,2 62,2 67,3 72,4 77,5 82,6 87,7 92,8 97,9 103,0
1105 27,4 32,6 37,9 43,1 48,4 53,6 58,8 64,1 69,3 74,6 79,8 85,1 90,3 95,6 100,8 106,1
order samPle
AvAntAge 1V 60 600 385 VD48 FDCB GFV-PB
61 2 3 4 5
1 Type of shutter
2 Width of damper
3 Height of damper
4 Type of magnet
5 Options: bipolar switches Rearmation Motor (ME)
6 GFV-PB: Finishing grill
13
Smoke evacuation shutter (remote-controlled)Avantage V13-C02/2013
Rf- Technologies Lange Ambachtstraat 40 9860 Oosterzele Belgique
1812-CPD
DÉCLARATION DE CONFORMITÉ
Date & lieu de délivrance: Signature: Oosterzele, 5 décembre 2012 Tom Van Leuven Directeur Technique
Nous, RF-Technologies NV déclarons sous notre seule responsabilité que le produit : Volet de désenfumage Avantage auquel se rapporte la présente déclaration, est conforme aux spécifications essentielles conformément à la norme EN 12101-8:2011 et autres dispositions de la directive du Conseil européen (89/106/CEE).
Déclaration basée sur le certificat de conformité n°1812-CPD-1042 d’Efectis.
Avantage Volet de désenfumage
Organes de commande / mécanisme de commande : - Commande manuelle par serrure et déclenchement électrique par démagnétisation de ventouse - Détection de position par capteurs de position - Maintien position ouverte par bras en acier plié
Résistance au feu selon EN 1366-10 et classification selon EN 13501-4:
Gamme Type Paroi Classification
1V (1 vantail): 300x385 mm jusqu’à 700x1075 mm
2V (2 vantaux):
350x385 mm jusqu’à 1100x1105 mm
Avantage 60 Conduit Promatect L500 30 mm EI 60 (ved i o) S 1500 AA multi Conduit Geoflam 30 mm EI 60 (ved i o) S 1500 AA multi Conduit Exthamat 45 mm EI 60 (ved i o) S 1500 AA multi
Avantage 120 Conduit Promatect L500 50 mm EI 120 (ved i o) S 1500 AA multi Conduit Geoflam 45mm EI 120 (ved i o) S 1500 AA multi Conduit Exthamat 45 mm EI 120 (ved i o) S 1500 AA multi
Conditions nominales d’activation/sensibilité
Conforme – activation automatique
Délai de réponse (temps de réponse) -
Conforme – activation automatique
Température de fonctionnement élevée selon EN 12101-8 § 4.2.1.3 PND
Fiabilité de fonctionnement -
300 cycles sans charge
Durabilité - du délai de réponse - de la fiabilité de fonctionnement
Conforme
Accessoires validés: - Pré-cadre de type KAP - Ajout de mastic entre le cadre du volet et le conduit - Réarmement à l’aide d’un moteur de type VAME
CE-D_V13 _FR_A 01/2013