panneaux sandwichs de couverture ondatherm...

Post on 11-Sep-2018

230 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

TRANSCRIPT

Panneaux sandwichs de couverture Ondatherm T

Nuance d’acier

Type de protection

CARACTERISTIQUES DES PAREMENTS NORMES

S 350 GD

Acier Revêtu Prélaqué

NF EN 10346

NF EN 10169XP P34-301

COUVERTURE POUR LOCAUX A FAIBLE OU MOYENNE HYGROMETRIE

28épaisseurnominale

Largeur utile : 1000

largeur hors tout : 1080 mm

2260,56039 25

30

Epaisseur parement extérieur (mm)

Epaisseur parement intérieur (mm)

Largeur utile

Largeur hors tout

Longueur maximale hors tout

Débord en extrémité

Ex. en épaisseurs 0,63 et 0,50 mm

Isolement : Indice d'affaiblissement (60mm)

Epaisseurs nominales de l'âme (mm)

40 50 60 80 100 120

DIMENSIONNELLES

PONDERALES (kg/m2)

ACOUSTIQUES

REACTION AU FEU

CARACTERISTIQUES DU PANNEAU

0,50 - 0,63 - 0,75

0,50 - 0,63

1000 mm

1080 mm

16000 mm

50 -100 - 150 - 200 - 300 mm

11,28 11,67 12,07 12,46 13,24 14,81

Rw (C;Ctr) : 25(-1;-3) dB

Transmission thermique Uc (W/m2.K)

Déperdition linéique ψ (W/m.K)

THERMIQUES

0,683

B-s2,d0 (exigence M1)

0,526 0,428 0,360 0,274 0,186

Le cœfficient de transmission thermique moyen Up doit être calculé selon les règles Th-U, fascicules parois opaques, d'après la formule suivante :

Uc est le cœfficient thermique en partie courante du panneau

ψj est le cœfficient de déperdition linéique correspondant à l'emboitement du panneau

Lp est la longueur d'emboîtement entre panneaux

n est le nombre de fixations

χ est le cœfficient de déperdition ponctuel par fixations (χ = 0,01 W/K)

A est l'aire de la paroi

Up = ψj x Lp + n x χA

DENSITE DE L’ISOLANT

TYPE D’ISOLANT

40 kg/m3 (± 5 kg/m3)

Mousse de Polyisocyanurate (PIR) sans HCFC (Hydro-Chloro-Fluoro-Carbone)

0,017 0,009 0,006 0,005 0,004 0,004

14,03

0,222

0,004

Uc +

Mousse de Polyisocyanurate sans HCFC (PIR)

Euroclasses selon NF EN 13501-1

Bande de chant en mousse polyéthylène

0,160

0,004

140

15,60

Selon DTA en vigueur

ArcelorMittal Construction France Edition N°1 Février 2015

ETPM en vigueur

Résistance thermique R (m².K/W) 1,35 1,80 2,25 2,65 3,55 5,304,40 6,15

Fixation complète - Pour fixation réduite en appui intermédiaire, nous consulter. Pour climat de montagne, nous consulter

Mousse de Polyisocyanurate sans HCFC (PIR)

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSIONDEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

2 APPUIS

100

TABLEAU D’UTILISATION

Portées admissibles pour épaisseurs de parements 0,50 - 0,50 mm

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

50

60

70

80

90

100

110

130

140

250

150

175

200

225

120

3 APPUIS

Epaisseurs du panneau (mm) ChargesdaN/m²80 60

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

Epaisseurs du panneau (mm)

50 40 30 30 40 50 60 80 100

120 / 140120 / 140

ArcelorMittal Construction France Edition N°1 Février 2015

FILM DE PROTECTIONLe film polyéthylène mis en place en usine devra être enlevé au fur et à mesure de la pose et au plus tard 3 mois après la mise à disposition de la marchandise en usine.PERÇAGES ET DECOUPESDans la mesure du possible, éviter toute découpe sur site.Afin de limiter les risques de désolidarisation mousse-métal lors d'une opération de découpe, il est conseillé de poser le panneau sur des appuis de telle sorte que les parements extérieur et intérieur soient maintenus de part et d'autre de la découpe (matériel conseillé : scie sauteuse).Lors d'une opération de découpe, protéger la zone environnante afin d'éviter de détériorer le revêtement des panneaux. Après toute opération de découpe ou perçage, il conviendra de balayer immédiatement les panneaux afin d'éliminer toutes limailles ou copeaux.

CALEPINAGEAvant toute commande, veuillez apporter une attention particulière au calepinage qui sera garant d'une mise en œuvre correcte et rapide.

Panneaux sandwichs de couverture Ondatherm T Selon NF EN 1991-1-3 et NF EN 1991-1-4, leurs

modificatifs et annexes nationales (EUROCODE)

3,993,993,993,993,993,993,993,993,903,993,723,983,593,593,473,263,362,993,262,763,182,572,992,182,761,902,461,682,231,50

4,664,664,664,664,574,664,474,664,324,664,134,373,984,023,853,723,723,483,613,263,523,043,302,583,072,242,741,982,481,77

5,335,335,335,335,145,334,945,334,755,134,554,754,384,444,224,184,093,963,963,773,853,513,622,983,392,593,022,292,742,05

6,006,006,006,005,726,005,425,835,175,454,965,144,774,874,604,644,454,454,314,274,193,983,933,383,702,933,302,592,992,32

6,50 6,506,506,506,506,506,346,326,025,915,755,575,515,285,304,935,114,514,934,274,773,984,413,384,122,933,882,593,672,32

6,506,506,506,506,506,506,506,506,506,506,266,046,005,585,785,145,574,715,384,345,214,044,843,434,532,974,282,634,062,36

7,007,007,00 7,007,007,007,007,007,007,006,776,516,495,876,255,346,034,905,834,525,654,205,263,574,943,104,672,744,452,46

3,993,993,773,993,583,993,433,993,293,993,173,993,073,992,973,992,893,992,813,992,743,992,603,752,473,502,373,292,233,04

4,454,664,194,663,974,663,794,663,634,663,504,663,384,663,274,663,184,593,094,413,014,252,853,932,703,612,593,332,463,04

4,905,334,605,334,365,334,165,333,985,333,825,333,695,243,575,003,464,793,374,613,284,453,094,102,943,732,813,362,683,05

5,366,005,026,004,756,004,526,004,326,004,155,764,005,473,875,223,755,003,654,813,554,643,344,283,173,843,033,402,913,05

5,916,505,586,505,306,505,076,504,876,504,706,344,556,024,415,754,295,514,165,294,025,103,734,433,493,853,293,413,123,06

6,506,506,296,506,076,505,836,505,636,505,456,505,296,505,146,215,015,824,885,474,765,184,434,444,173,873,953,423,763,06

7,007,007,007,006,847,006,597,006,387,006,197,006,027,005,876,675,736,125,605,655,495,255,134,464,843,884,603,434,393,07

Panneaux sandwiches de couverture

Mousse de Polyisocyanurate sans HCFC (PIR)TABLEAU D’UTILISATION

ArcelorMittal Construction France Edition N°1 Février 2015

REFERENTIEL NV65 Modifiées 2009 CONTRAINTES ADMISSIBLES Ondatherm T

Fixation complète - Pour fixation réduite en appui intermédiaire, nous consulter.

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSIONDEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

2 APPUIS

100

Portées admissibles pour épaisseurs de parements 0,50 - 0,50 mm

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

50

60

70

80

90

100

110

130

140

250

150

175

200

225

120

3 APPUIS

Epaisseurs du panneau (mm) ChargesdaN/m²80 60

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

PRESSION

DEPRESSION

Epaisseurs du panneau (mm)

50 40 30 30 40 50 60 80 100

120 / 140120 / 140

5,025,504,695,424,404,954,154,463,923,903,733,473,603,123,492,843,392,603,302,403,222,233,031,892,821,642,651,452,491,30

5,505,505,155,504,855,274,594,794,354,304,153,914,003,603,873,343,753,083,652,843,562,643,312,243,071,942,861,712,681,54

5,505,505,505,505,305,505,035,124,794,704,574,364,404,074,243,844,103,563,993,293,893,053,582,583,312,243,081,982,871,77

6,006,006,006,005,745,905,475,455,225,095,004,804,804,554,614,334,464,044,343,734,233,463,862,933,552,543,292,243,062,01

6,50 6,506,506,506,506,416,395,926,115,535,805,215,504,795,234,344,994,044,773,734,573,464,142,933,902,543,712,243,542,01

6,506,506,506,506,506,506,506,466,455,856,165,355,894,885,654,435,444,065,243,755,073,484,692,964,402,574,162,273,952,03

7,007,007,007,007,007,007,007,006,806,176,535,506,284,966,074,525,884,155,713,845,563,575,233,034,902,644,612,344,352,09

4,015,503,785,503,605,503,445,463,305,113,184,823,084,572,994,362,914,172,834,012,773,862,623,562,493,272,382,892,282,60

4,475,504,215,503,995,503,815,503,645,363,515,053,404,793,304,573,214,373,124,203,054,052,883,632,733,272,612,892,502,60

4,935,504,645,504,395,504,185,503,995,503,845,293,715,013,604,783,504,573,414,393,334,233,143,692,983,272,842,892,722,60

5,396,005,066,004,796,004,556,004,335,864,165,524,035,243,914,993,804,773,704,583,604,423,403,763,223,283,072,902,932,60

5,916,505,596,505,336,505,116,504,916,494,736,114,585,794,445,514,315,154,194,774,074,433,813,773,593,283,392,913,212,61

6,506,506,366,506,096,505,856,505,646,505,466,495,306,005,155,585,025,174,904,784,784,454,493,784,253,294,032,913,842,61

7,007,007,007,006,847,006,597,006,387,006,196,886,026,215,875,655,735,195,604,805,494,465,173,794,913,304,672,924,462,62

FILM DE PROTECTIONLe film polyéthylène mis en place en usine devra être enlevé au fur et à mesure de la pose et au plus tard 3 mois après la mise à disposition de la marchandise en usine.PERÇAGES ET DECOUPESDans la mesure du possible, éviter toute découpe sur site.Afin de limiter les risques de désolidarisation mousse-métal lors d'une opération de découpe, il est conseillé de poser le panneau sur des appuis de telle sorte que les parements extérieur et intérieur soient maintenus de part et d'autre de la découpe (matériel conseillé : scie sauteuse).Lors d'une opération de découpe, protéger la zone environnante afin d'éviter de détériorer le revêtement des panneaux. Après toute opération de découpe ou perçage, il conviendra de balayer immédiatement les panneaux afin d'éliminer toutes limailles ou copeaux.

CALEPINAGEAvant toute commande, veuillez apporter une attention particulière au calepinage qui sera garant d'une mise en œuvre correcte et rapide.

top related