delta din rail power supplies - ferret.com.au · 23 drp048v480w1bn ac-dc din rail 48 volt 480 watts...
Post on 12-May-2020
0 Views
Preview:
TRANSCRIPT
1
Delta DIN Rail Power Supplies
2
3
4 Introduction Delta Cliq and Cliq II Series
5 DRC-12V10W1AZ AC-DC DIN RAIL 12 VOLT 10 WATTS
6 DRC-12V30W1AZ AC-DC DIN RAIL 12 VOLT 30 WATTS
7 DRC-12V60W1AZ AC-DC DIN RAIL 12 VOLT 54 WATTS
8 DRC-24V10W1AZ AC-DC DIN RAIL 24 VOLT 10 WATTS
9 DRC-24V30W1AZ AC-DC DIN RAIL 24 VOLT 30 WATTS
10 DRC-24V60W1AZ AC-DC DIN RAIL 24 VOLT 60 WATTS
11 DRC-24V100W1AZ AC-DC DIN RAIL 24 VOLT 91 WATTS
12 DRP012V015W1AZ AC-DC DIN RAIL 12 VOLT 15 WATTS
13 DRP012V030W1AZ AC-DC DIN RAIL 12 VOLT 30 WATTS
14 DRP012V060W1AZ AC-DC DIN RAIL 12 VOLT 60 WATTS
15 DRP012V100W1AA AC-DC DIN RAIL 12 VOLT 100 WATTS
16 DRP024V060W1BN AC-DC DIN RAIL 24 VOLT 60 WATTS
17 DRP024V120W1BN AC-DC DIN RAIL 24 VOLT 120 WATTS
18 DRP024V240W1BN AC-DC DIN RAIL 24 VOLT 240 WATTS
19 DRP024V480W1BN AC-DC DIN RAIL 24 VOLT 480 WATTS
20 DRP048V060W1BN AC-DC DIN RAIL 48 VOLT 60 WATTS
21 DRP048V120W1BN AC-DC DIN RAIL 48 VOLT 120 WATTS
22 DRP048V240W1BN AC-DC DIN RAIL 48 VOLT 240 WATTS
23 DRP048V480W1BN AC-DC DIN RAIL 48 VOLT 480 WATTS
24 DRB-24V020AB BUFFER MODULE DIN RAIL 20 AMP
26 DRR20, DRR40 REDUNDANCY MODULES DIN RAIL 20A & 40A
28 DRU24V40ABN DC-UPS MODULE DIN RAIL 20V 40A
30 DRP024V0603BN AC-DC DIN RAIL 24 VOLT 60 WATTS 3 PhASE
31 DRP024V1203BN AC-DC DIN RAIL 24 VOLT 120 WATTS 3 PhASE
32 DRP024V2403BN AC-DC DIN RAIL 24 VOLT 240 WATTS 3 PhASE
33 DRP024V4803BN AC-DC DIN RAIL 24 VOLT 480 WATTS 3 PhASE
34 DRP024V9603BN AC-DC DIN RAIL 24 VOLT 960 WATTS 3 PhASE
Contents
4
The CliQ and CliQ II series DIN Rail Power Supply are the latest offerings from one of the world’s largest leading power supply manufacturers and solution providers –Delta. The state-of-the-art design is made to withstand harsh industrial environments. The rugged, compact metal case and plastic case are both shock and vibration resistant according to IEC60068-2.
The CliQ and CliQ II series of products provide overvoltage, overload and over temperature protections. Using a wide input voltage range design, the power supplies are usable worldwide.
The built in Power Boost feature is the reserve power available constantly that allows reliable startup of loads with high inrush current.
Highlights• Fast wiring and easy installation• Compact design for easy handling• Power Boost 150%: for 3 seconds (CliQ) for 5
seconds (CliQ II)• Overload, overvoltage, and over temperature
protections• Vibration IEC60068-2-6• Cooling: Convection• RoHS Compliant• With Conformal Coating (Class 1 Div. 2 Ready)• Expected life time: 10 years
Typical Applications• General engine constructions• Apparatus constructions• Building equipments• Packing equipments• Wood-working machines• Sheet-fabricating machines• Automotive engineering• Test & Measurement• Environmental engineering• Construction machines• Automation process
The products in the CliQ and CliQ II Series come with conformal coating as standard, making them suitable for applications where dust, moisture, hazardous chemical particles and condensation are prevalent.
Redundancy SolutionThe Redundancy Solution ensures zero system down time for the customer when one of the power supply fails or is being disconnected unexpectedly. Under normal circumstances, both power supplies are each operating at approximately 50% load. When one fails, the other automatically takes over, thus providing 100% load and ensures that the system continues running.
The fault relay function alerts the user of any failure through potential free contacts. The LED lights on the Redundancy Modules (see page 24) also indicate the health of each individual power supply.
IntroductionDELTA CLIQ AND CLIQ II SERIES
5
Delta DRC-12V10W1AZAC-DC DIN RAIL 12 VOLT 10 WATTS
Features
• Protection Class II, Double Isolation (No Earth connection is required)
• Universal AC input voltage and full power up to 55°C• Power will not de-rate for the entire input voltage range• Efficiency > 82.0% @ 115Vac & 230Vac• NEC Class 2 / Limited Power Source (LPS) certified• Overvoltage / Overcurrent / Over Temperature Protections
MECHANICAL
Dimensions (LxWxH)
91 x 18 x 55.6mm
Case Cover Plastic
Weight 0.06kg
Indicator Green LED (DC OK)
Cooling System Convection
Input Terminal M4 x 2 Pins (Rated 300V/16A)
Output Terminal M4 x 2 Pins (Rated 300V/16A)
Input/Output Wire AWG 26-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
STANDARDS & APPROVALS
Safety TUV Bauart to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
Class 2 Power Supply
UL/cUL recognized to UL 60950-1, CSA C22.2 No. 60950-1
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation 3.0KVAC
ENVIRONMENTAL
Operating Temp -25°C to +71°C
Power De-rating > 55°C de-rate power by 2.5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 90–264VAC 125-375 VDC
Current < 0.30A@115VAC, < 0.20A @ 230VAC
Frequency 47-63Hz
Efficiency at 100% load > 82.0% @ 115VAC & 230VAC
Max. Inrush current < 15A @ 115VAC, < 30A @ 230VAC
Leakage current < 0.25mA @ 240VAC
OUTPUT
Voltage 12V
Current 0.83A
Power 10W
Line regulation < 1% typ. (@ 90-264VAC, 100% load)
Load regulation < 2% typ. (@ 90-264VAC, 100% load)
Residual Ripple / PARD (20MHz)
< 50mVpp /150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 3,000ms @ nominal input (100% load)
Hold-up Time > 10ms @ 115VAC > 30ms @ 230VAC (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000μF Max.
6
Delta DRC-12V30W1AZAC-DC DIN RAIL 12 VOLT 30 WATTS
Features
• Protection Class II, Double Isolation (no earth connection required)
• Universal AC input voltage and full power up to 55°C• Efficiency > 85.0% @ 115VAC & 230VAC• NEC Class 2 / Limited Power Source (LPS) certified• Overvoltage/Overcurrent/Over Temperature Protections• International safety approvals to ITE and Industrial standards
MECHANICAL
Dimensions (LxWxH)
91 x 53 x 55.6mm
Case Cover Plastic
Weight 0.14kg
Indicator Green LED (DC OK)
Cooling System Convection
Input Terminal 2 Pins (Rated 300V/25A)
Output Terminal 4 Pins (Rated 300V/25A)
Input/Output Wire AWG 24-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
STANDARDS & APPROVALS
Safety TUV Bauart to EN 60950-1, UL/cUL recognised to UL 60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
Class 2 Power Supply
UL/cUL recognized to UL 60950-1, CSA C22.2 No. 60950-1
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation 3.0KVAC
ENVIRONMENTAL
Operating Temp -25°C to +71°C
Power De-rating > 55°C de-rate power by 2.5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 90–264VAC 125–375VDC
Current < 0.80A@115VAC, < 0.60A @ 230VAC
Frequency 47-63Hz
Efficiency at 100% load > 85.0% @ 115VAC & 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 25A @ 115VAC, < 50A @ 230VAC
Leakage current < 0.25mA @ 240VAC
OUTPUT
Voltage 12V
Output Voltage Range 11.5–14.5VDC
Current 2.1A
Power 30W
Line regulation < 1% typ. (@ 90-264VAC 100% load)
Load regulation < 2% typ. (@ 90-264VAC, 100% load)
PARD (20MHz) 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 3,000ms @ nominal input (100% load)
Hold-up Time > 25ms @ 115VAC, > 30ms @ 230VAC (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000μF Max.
7
Delta DRC-12V60W1AZAC-DC DIN RAIL 12 VOLT 54 WATTS
Features
• Protection Class II, Double Isolation (No earth connection required)
• Universal AC input voltage and full power up to 55°C• Efficiency > 85.0% @ 115Vac & 230VAC• NEC Class 2/Limited Power Source (LPS) certified• Overvoltage/Overcurrent/Over Temperature Protections• International safety approvals to ITE and Industrial standard
MECHANICAL
Dimensions (LxWxH)
91 x 71 x 55.6mm
Case Cover Plastic
Weight 0.22kg
Indicator Green LED (DC OK)
Cooling System Convection
Input Terminal 2 Pins (Rated 300V/25A)
Output Terminal 4 Pins (Rated 300V/25A)
Input/Output Wire AWG 26-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
STANDARDS & APPROVALS
Safety TUV Bauart to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation 3.0KVAC
ENVIRONMENTAL
Operating Temp -25°C to +71°C
Power De-rating > 55°C de-rate power by 2.5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 90–264VAC 125–375VDC
Current < 1.50A@115VAC, < 0.80A @ 230VAC
Frequency 47–63Hz
Efficiency at 100% load > 85.0% @ 115VAC & > 87.0% 230VAC
Max. Inrush current < 30A @ 115VAC, < 60A @ 230VAC
Leakage current < 0.25mA @ 240VAC
OUTPUT
Voltage 12V
Voltage range 11.5–14.0V
Current 4.50A
Power 54W
Line regulation < 1% typ. (@ 90-264VAC, 100% load)
Load regulation < 2% typ. (@ 90-264VAC, 100% load)
PARD (20MHz) < 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 3,000ms @ nominal input (100% load)
Hold-up Time > 16ms @ 115VAC > 30ms @ 230VAC (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000μF Max.
8
Delta DRC-24V10W1AZAC-DC DIN RAIL 24 VOLT 10 WATTS
Features
• Protection Class II, Double Isolation (no earth connection required)
• Universal AC input voltage and full power up to 55°C• Efficiency > 80.0% @ 115VAC & 230VAC• NEC Class 2 / Limited Power Source (LPS) certified• Overvoltage/Overcurrent/Over Temperature Protections• International safety approvals to ITE and Industrial standards
MECHANICAL
Dimensions (LxWxH)
91 x 18 x 55.6mm
Case Cover Plastic
Weight 0.065kg
Indicator Green LED (DC OK)
Cooling System Convection
Input Terminal 2 Pins (Rated 300V/16A)
Output Terminal 4 Pins (Rated 300V/16A)
Input/Output Wire AWG 26-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
STANDARDS & APPROVALS
Safety TUV Bauart to EN 60950-1, UL/cUL recognised to UL 60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation 3.0KVAC
ENVIRONMENTAL
Operating Temp -25°C to +71°C
Power De-rating > 55°C de-rate power by 2.5% / °C
Humidity 0–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 90–264VAC 125–375VDC
Current < 0.30A@115VAC, < 0.20A @ 230VAC
Efficiency at 100% load > 80.0% @ 115VAC & 230VAC
Frequency 47-63Hz
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 15A @ 115VAC, < 30A @ 230VAC
Leakage current < 0.25mA @ 240VAC
OUTPUT
Voltage 24V
Current 0.42A
Power 10W
Line regulation < 1% typ. (@ 90-264VAC 100% load)
Load regulation < 2% typ. (@ 90-264VAC, 100% load)
PARD (20MHz) 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 3,000ms @ nominal input (100% load)
Hold-up Time > 10ms @ 115VAC, > 30ms @ 230VAC (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000μF Max.
9
Delta DRC-24V30W1AZAC-DC DIN RAIL 30 WATTS
Features
• Protection Class II, Double Isolation (No Earth connection is required)
• Universal AC input voltage and full power up to 55°C• Power will not de-rate for the entire input voltage range• Efficiency > 87.0% @ 115VAC & 230VDC• NEC Class 2 / Limited Power Source (LPS) certified• Overvoltage / Overcurrent / Over Temperature Protections
MECHANICAL
Dimensions (LxWxH)
91 x 53 x 55.6mm
Case Cover Plastic
Weight 0.14kg
Indicator Green LED (DC OK)
Cooling System Convection
Input Terminal 2 Pins (Rated 300V/25A)
Output Terminal 4 Pins (Rated 300V/25A)
Input/Output Wire AWG 24-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
STANDARDS & APPROVALS
Safety TUV Bauart to EN 60950-1, UL/cUL recognized to UL 60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
Class 2 Power Supply
UL/cUL recognized to UL 60950-1, CSA C22.2 No. 60950-1
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation 3.0KVAC
ENVIRONMENTAL
Operating Temp -25°C to +71°C
Power De-rating > 55°C de-rate power by 2.5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 90–264VAC 125-375 VDC
Current < 0.80A@115Vac, < 0.60A @ 230VAC
Frequency 47-63Hz
Efficiency at 100% load > 87.0% @ 115VAC & 230VAC
Max. Inrush current < 25A @ 115VAC, < 50A @ 230VAC
Leakage current < 0.25mA @ 240VAC
OUTPUT
Voltage 24V
Output Voltage Range 23.52-24.48VDC
Current 1.25A
Power 30W
Line regulation < 1% typ. (@ 90-264VAC 100% load)
Load regulation < 2% typ. (@ 90-264VAC, 100% load)
PARD (20MHz) 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 3,000ms @ nominal input (100% load)
Hold-up Time > 25ms @ 115VAC, > 30ms @ 230VAC (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000μF Max.
10
Delta DRC-24V60W1AZAC-DC DIN RAIL 60 WATTS
Features
• Protection Class II, Double Isolation (No Earth connection is required)
• Universal AC input voltage and full power up to 55°C• Power will not de-rate for the entire input voltage range• Efficiency > 88.0% @ 115VAC & 230VDC• NEC Class 2 / Limited Power Source (LPS) certified• Overvoltage / Overcurrent / Over Temperature Protections
MECHANICAL
Dimensions (LxWxH)
91 x 71 x 55.6mm
Case Cover Plastic
Weight 0.24kg
Indicator Green LED (DC OK)
Cooling System Convection
Input Terminal 2 Pins (Rated 300V/25A)
Output Terminal 4 Pins (Rated 300V/25A)
Input/Output Wire AWG 22-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
STANDARDS & APPROVALS
Safety TUV to EN 60950-1, UL/cUL recognized to UL 60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
Class 2 Power Supply
UL/cUL recognized to UL 60950-1, CSA C22.2 No. 60950-1
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation 3.0KVAC
ENVIRONMENTAL
Operating Temp -25°C to +71°C
Power De-rating > 55°C de-rate power by 2.5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 90–264VAC 125-375 VDC
Current < 1.50A@115VAC, < 1.00A @ 230VAC
Frequency 47-63Hz
Efficiency at 100% load > 88.0% @ 115VAC & 230VAC
Max. Inrush current < 30A @ 115VAC, < 60A @ 230VAC
Leakage current < 0.25mA @ 240VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28VDC
Current 2.50A
Power 60W
Line regulation < 1% typ. (@ 90-264VAC 100% load)
Load regulation < 2% typ. (@ 90-264VAC, 100% load)
PARD (20MHz) 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 3,000ms @ nominal input (100% load)
Hold-up Time > 16ms @ 115VAC, > 30ms @ 230VAC (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000μF Max.
11
Delta DRC-24V100W1AZAC-DC DIN RAIL 91 WATTS
Features
• Protection Class II, Double Isolation (No earth connection required)
• Universal AC input voltage and full power up to 55°C• Efficiency > 87.0% @ 115VAC, > 89.0% 230VAC• NEC Class 2/Limited Power Source (LPS) certified• Overvoltage/Overcurrent/Over Temperature Protections• International safety approvals to ITE and Industrial standard
MECHANICAL
Dimensions (LxWxH)
91 x 89.9 x 55.6mm
Case Cover Plastic
Weight 0.33kg
Indicator Green LED (DC OK)
Cooling System Convection
Input Terminal 2 Pins (Rated 300V/25A)
Output Terminal 4 Pins (Rated 300V/25A)
Input/Output Wire AWG 22-12 (x1), AWG 24-12 (x2)
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
STANDARDS & APPROVALS
Safety TUV Bauart to EN 60950-1, UL/cUL recognised to UL60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, Limited Power Source (LPS)
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation 3.0KVAC
ENVIRONMENTAL
Operating Temp -25°C to +71°C
Power De-rating > 55°C de-rate power by 2.5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 90–264VAC 125-375 VDC
Current < 2.20A@115VAC, < 1.00A @ 230VAC
Frequency 47–63Hz
Efficiency at 100% load > 87.0% @ 115VAC > 89.0% @ 230VAC
Max. Inrush current < 30A @ 115VAC, < 60A @ 230VAC
Leakage current < 0.25mA @ 240VAC
OUTPUT
Voltage 24V
Voltage range 20–24.48V
Current 3.80A
Power 91W
Line regulation < 1% typ. (@ 90-264VAC, 100% load)
Load regulation < 2% typ. (@ 90-264VAC, 100% load)
PARD (20MHz) < 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 3,000ms @ nominal input (100% load)
Hold-up Time > 10ms @ 115VAC > 30ms @ 230VAC (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
3,000μF Max.
12
Delta DRP012V015W1AZAC-DC DIN RAIL 12 VOLT 15 WATTS
Features
• Universal AC input voltage without power de-rating• Power Boost of 150% for 3 seconds• Reliable design, expected life of 10 years• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Multiple wire connections to terminals allowed• Conformal coating on PCBA to protect against chemical
and dust pollutants• Hazardous Locations approval to ATEX and Class I, Div 2
MECHANICAL
Dimensions (LxWxH)
100 x 32 x 100.6mm
Case Cover Plastic
Weight 0.18kg
Cooling System Convection
Input Terminal M3.5 x 5 Pins (Rated 300V/15A)
Output Terminal M3.5 x 5 Pins (Rated 300V/15A)
Input/Output Wire AWG 22-14
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -20°C to +75°C
Power De-rating > 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 4% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 0.37A@115VAC, < 0.22A @ 230VAC
Frequency 47-63Hz
Efficiency1 at 100% load > 84.0% @ 115VAC > 83.0% @ 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 30A @ 115VAC, < 65A @ 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 12V
Output Voltage Range 11–14V
Current 1.25A
Power 15W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 100mVpp
Hold-up Time > 22ms @ 115VAC > 110ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115Vac,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety TUV Bauart to EN60950-1, UL/cUL recognised to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
Hazardous Location / ATEX
(For DRP012V015W1AY) cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 12.12.01:2007 Class I, Division 2, Group A,B,C,D T4 EN60079-0:2009, EN60079-15:2010 (Ex II 3GII 3G Ex nA IIC T4 Gc)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP012V015W1AY: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
13
Delta DRP012V030W1AZAC-DC DIN RAIL 12 VOLT 30 WATTS
Features
• Universal AC input voltage without power de-rating• Power Boost of 150% for 3 seconds• Reliable design, expected life of 10 years• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Multiple wire connections to terminals allowed• Conformal coating on PCBA to protect against chemical
and dust pollutants• Hazardous Locations approval to ATEX and Class I, Div 2
MECHANICAL
Dimensions (LxWxH)
100 x 32 x 100.6mm
Case Cover Plastic
Weight 0.20kg
Cooling System Convection
Input Terminal M3.5 x 5 Pins (Rated 300V/15A)
Output Terminal M3.5 x 5 Pins (Rated 300V/15A)
Input/Output Wire AWG 22-14
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -20°C to +75°C
Power De-rating > 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 4% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–3,000m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 0.70A@115VAC, < 0.42A @ 230VAC
Frequency 47-63Hz
Efficiency1 at 100% load > 85.0% @ 115VAC & 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 40A @ 115VAC, < 80A @ 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 12V
Output Voltage Range 11–14V
Current 2.50A
Power 30W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 100mVpp
Hold-up Time > 22ms @ 115VAC > 110ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115Vac,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety TUV Bauart to EN60950-1, UL/cUL recognised to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
Hazardous Location / ATEX
(For DRP012V030W1AY) cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 12.12.01:2007 Class I, Division 2, Group A,B,C,D T4 EN60079-0:2009, EN60079-15:2010 (Ex II 3GII 3G Ex nA IIC T4 Gc)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP012V030W1AY: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
14
Delta DRP012V060W1AAAC-DC DIN RAIL 12 VOLT 60 WATTS
Features
• Universal AC input voltage without power de-rating• Power Boost of 150% for 3 seconds• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Multiple wire connections to terminals allowed• Conformal coating on PCBA to protect against chemical
and dust pollutants• Hazardous Locations approval to ATEX and Class I, Div 2
MECHANICAL
Dimensions (LxWxH)
121 x 32 x 120mm
Case Cover Aluminium
Weight 0.33kg
Cooling System Convection
Input Terminal M4 x 3 Pins (Rated 300V/20A)
Output Terminal M4 x 2 Pins (Rated 300V/20A)
Input/Output Wire AWG 22-14
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -20°C to +75°C
Power De-rating > 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 4% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–3,000m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 1.35A@115VAC, < 0.08A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 80.0% @ 115VAC & 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 50A @ 115VAC, < 100A @ 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 12V
Output Voltage Range 11–14V
Current 5.00A
Power 60W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 100mVpp
Hold-up Time > 22ms @ 115VAC > 110ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115Vac,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety TUV Bauart to EN60950-1, UL/cUL recognised to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
Ex II 3G ATEX 97/9/EC
Certificate No. EPS 12 ATEX 1 491 X
Hazardous Location / ATEX
cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 12.12.01:2007 Class I, Division 2, Group A,B,C,D T4, EN60079-0:2009, EN60079-15:2010 (Ex II 3GII 3G Ex nA IIC T4 Gc)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
15
Delta DRP012V100W1AAAC-DC DIN RAIL 12 VOLT 100 WATTS
Features
• Universal AC input voltage without power de-rating• Power Boost of 150% for 3 seconds• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Multiple wire connections to terminals allowed• Conformal coating on PCBA to protect against chemical
and dust pollutants• Hazardous Locations approval to ATEX and Class I, Div 2
MECHANICAL
Dimensions (LxWxH)
121 x 50 x 118.7mm
Case Cover Aluminium
Weight 0.64kg
Cooling System Convection
Input Terminal M4 x 3 Pins (Rated 300V/20A)
Output Terminal M4 x 2 Pins (Rated 300V/20A)
Input/Output Wire AWG 18-14
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -20°C to +75°C
Power De-rating > 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 4% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–3,000m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 2.50A@115VAC, < 1.50A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 85.5% @ 115VAC > 87.5% @ 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 100A @ 115VAC, No damage @ 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 12V
Output Voltage Range 11–14V
Current 8.33A
Power 100W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 100mVpp
Hold-up Time > 22ms @ 115VAC > 110ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115Vac,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety TUV Bauart to EN60950-1, UL/cUL recognised to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01
ExII 3G ATEX 97/9/EC
Certificate No. EPS 12 ATEX 1 491 X
Hazardous Location / ATEX
cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 12.12.01:2007 Class I, Division 2, Group A,B,C,D T4 EN60079-0:2009, EN60079-15:2010 (Ex II 3GII 3G Ex nA IIC T4 Gc)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
16
Delta DRP024V060W1BNAC-DC DIN RAIL 24 VOLT 60 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 90.0% @ 230VAC• Power Boost of 150% for 5 seconds• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• IP20 compliant, pluggable AC and DC terminal blocks• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
120.6 x 32 x 119.3mm
Case Cover Aluminium
Weight 0.33kg
Cooling System Convection
Input Terminal Pluggable connector 3 Pins (Rated 300V/30A)
Output Terminal Pluggable connector 2 Pins (Rated 300V/30A)
Input/Output Wire AWG 22-12
MTBF2 > 800,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +85°C
Power De-rating > 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 4% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 1.40A@115VAC, < 0.80A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 90% @ 115VAC & 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 20A @ 115VAC, 35A @ 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 2.50A
Power 60W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 150mVpp
Hold-up Time > 20ms @ 115VAC > 125ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Ex II 3G ATEX 97/9/EC IECEX Test Report
(For DRP024V060W1BA) Certificate No. ESP 12 ATEX 1 491 X; For IEC60079-0, IEC60079-15
Hazardous Location / ATEX (For DRP024V060W1BA)
CSA to CSA C22.2 No. 213-M1987, ANSI / ISA, 12.12.01:2007 (Class I, Division 2, Group A, B, C, D, T4 EN60079-0:2009, EN60079-15:2010 (Ex II 3G Ex nA nC IIc T4 Gc)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP024V060W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
17
Delta DRP024V120W1BNAC-DC DIN RAIL 24 VOLT 120 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 90.0% @ 230VAC• Power Boost of 150% for 5 seconds • Full corrosion resistant Aluminium chassis• IP20 compliant, pluggable AC and DC terminal blocks• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 50 x 123.1mm
Case Cover Aluminium
Weight 0.72kg
Cooling System Convection
Input Terminal Pluggable connector 3 Pins (Rated 300V/15A)
Output Terminal Pluggable connector 4 Pins (Rated 300V/15A)
Input/Output Wire AWG 20-12
MTBF2 > 800,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +85°C
Power De-rating > 50°C de-rate power by 2.5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 2.20A@115VAC, < 1.20A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 89.0% @ 115VAC > 90.0% @ 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 35A @ 115VAC & 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 5.00A
Power 120W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 150mVpp
Hold-up Time > 20ms @ 115VAC > 115ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP024V120W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
18
Delta DRP024V240W1BNAC-DC DIN RAIL 24 VOLT 240 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 92.0% @ 230VAC• Power Boost of 150% for 5 seconds • IP20 compliant, pluggable AC and DC terminal blocks• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Extreme low temperature cold start at -40°C• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 85 x 124.1mm
Case Cover Aluminium
Weight 1.10kg
Cooling System Convection
Input Terminal Pluggable connector 3 Pins (Rated 300V/15A)
Output Terminal Pluggable connector 4 Pins (Rated 300V/15A)
Input/Output Wire AWG 16-14
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating > 50°C de-rate power by 2.5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 2.50A@115VAC, < 1.30A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 90.0% @ 115VAC & 230VAC
Power Factor > 0.96 @ 115VAC > 0.90 230VAC
Max. Inrush current < 35A @ 115VAC & 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 10.00A
Power 240W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 150mVpp
Hold-up Time > 20ms @ 115VAC & 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP024V240W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
19
Delta DRP024V480W1BNAC-DC DIN RAIL 24 VOLT 480 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 90.0% @ 230VAC• Power Boost of 150% for 5 seconds (480W: 200% for 2
seconds)• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Extreme low temperature cold start at -40°C• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 144 x 118.6mm
Case Cover Aluminium
Weight 1.37kg
Cooling System Convection
Input Terminal M3 x 3 Pins (Rated 300V/30A)
Output Terminal M3 x 4 Pins (Rated 300V/30A)
Input/Output Wire I/P: AWG 18-10 O/P: AWG 18-10
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +75°C
Power De-rating > 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 5.00A@115VAC, < 3.00A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 91.0% @ 115VAC > 92.0% @ 230VAC
Power Factor > 0.96 @ 115VAC > 0.89 230VAC
Max. Inrush current < 35A @ 115VAC & 230VAC
Leakage current < 3mA @ 240VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current < 3mA @ 240VAC
Power 480W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 150mVpp
Hold-up Time > 20ms @ 115VAC & 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP024V480W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
20
Delta DRP048V060W1BNAC-DC DIN RAIL 48 VOLT 60 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 92.0% @ 230VAC• Power Boost of 150% for 5 seconds (480W: 200% for 2
seconds)• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Extreme low temperature cold start at -40°C• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 32 x 125mm
Case Cover Aluminium
Weight 0.38kg
Cooling System Convection
Input Terminal Pluggable connector 3 Pins (Rated 300V/15A)
Output Terminal Pluggable connector 4 Pins (Rated 300V/15A)
Input/Output Wire AWG 22-12
MTBF2 > 800,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating > 50°C de-rate power by 2.5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 1.40A@115VAC, < 0.80A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 91.0% @ 115VAC > 92.0% @ 230VAC
Power Factor Conforms to EN61000-3-2
Max. Inrush current < 20A @ 115VAC < 35A @ 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 48V
Output Voltage Range 48–56V
Current 1.25A
Power 60W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 200mVpp
Hold-up Time > 20ms @ 115VAC > 125ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Ex II 3G ATEX 97/9/EC IECEX
(For DRP048V060W1BA) Certificate No. EPS 12 ATEX 1 491 X
Hazardous Location / ATEX (For DRP048V060W1BA)
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (> +50°C derating)], EN 60079-0:2009, EN 60079-15:2010 [ II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C (> +50°C derating)]
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP048V060W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
21
Delta DRP048V120W1BNAC-DC DIN RAIL 48 VOLT 120 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 90.0% @ 230VAC• Power Boost of 150% for 5 seconds• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 50 x 123.1mm
Case Cover Aluminium
Weight 0.72kg
Cooling System Convection
Input Terminal Pluggable connector 3 Pins (Rated 300V/15A)
Output Terminal Pluggable connector 4 Pins (Rated 300V/15A)
Input/Output Wire AWG 20-12
MTBF2 > 800,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating > 50°C de-rate power by 2.5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 2.20A@115VAC, < 1.10A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 90.0% @ 115VAC & 230VAC
Power Factor > 0.99 @ 115VAC, > 0.93 @ 230VAC
Max. Inrush current < 35A @ 115VAC < 50A @ 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 48V
Output Voltage Range 48–56V
Current 2.5A
Power 120W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 200mVpp
Hold-up Time > 20ms @ 115VAC > 125ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Ex II 3G ATEX 97/9/EC IECEX
(For DRP048V120W1BA) Certificate No. EPS 12 ATEX 1 491 X
Hazardous Location / ATEX (For DRP048V120W1BA)
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (> +50°C derating)], EN 60079-0:2009, EN 60079-15:2010 [Ex II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C (> +50°C derating)]
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP048V120W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
22
Delta DRP048V240W1BNAC-DC DIN RAIL 48 VOLT 240 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 92% @ 230VAC• Power Boost of 150% for 5 seconds• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 85 x 124.1mm
Case Cover Aluminium
Weight 0.96kg
Cooling System Convection
Input Terminal Pluggable connector 3 Pins (Rated 300V/15A)
Output Terminal Pluggable connector 4 Pins (Rated 300V/15A)
Input/Output Wire AWG 20-12
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating > 50°C de-rate power by 2.5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage 85–264VAC 120–375VDC
Current < 2.50A@115VAC, < 1.30A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 90.0% @ 115VAC > 92.0% @ 230VAC
Power Factor > 0.96 @ 115VAC, > 0.90 @ 230VAC
Max. Inrush current < 35A @ 115VAC & 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 48V
Output Voltage Range 48–56V
Current 5.0A
Power 240W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 200mVpp
Hold-up Time > 20ms @ 115VAC > 115ms @ 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Ex II 3G ATEX 97/9/EC IECEX
(For DRP048V240W1BA) Certificate No. EPS 12 ATEX 1 491 X
Hazardous Location / ATEX (For DRP048V060W1BA)
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (Vertical:> +50°C derating, Horizontal: > +40°C derating)], EN 60079-0:2009, EN 60079-15:2010 [ II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C (Vertical:> +50°C derating, Horizontal: > +40°C derating)]
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP048V240W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
23
Delta DRP048V480W1BNAC-DC DIN RAIL 48 VOLT 480 WATTS
Features
• Universal AC input voltage without power de-rating• High efficiency > 93% @ 230VAC• Power Boost of 150% for 5 seconds• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 144 x 118.6mm
Case Cover Aluminium
Weight 1.37kg
Cooling System Convection
Input Terminal 3 Pins (Rated 300V/30A)
Output Terminal 4 Pins (Rated 300V/30A)
Input/Output Wire I/P: AWG 18-10 O/P: AWG 16-10
MTBF2 > 500,000 hrs
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating > 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,500m
SpecificationsINPUT
Voltage Range 85–264VAC 120–375VDC
Current < 5.00A@115VAC, < 3.00A @ 230VAC
Frequency 47–63Hz
Efficiency1 at 100% load > 91.0% @ 115VAC > 93.0% @ 230VAC
Power Factor > 0.96 @ 115VAC, > 0.90 @ 230VAC
Max. Inrush current < 35A @ 115VAC & 230VAC
Leakage current < 1mA @ 240VAC
OUTPUT
Voltage 48V
Output Voltage Range 48–56V
Current 10.0A
Power 480W
Line regulation < 0.5% typ. (@ 85-264VAC, 100% load)
Load regulation < 1% typ. (@ 85-264VAC, 0–100% load)
PARD (20MHz) < 200mVpp
Hold-up Time > 20ms @ 115VAC & 230VAC
NOTES: 1) Efficiency: O/P 100% load, Ta: 25°C at Vertical Mounting Orientation 2) MTBF as per Telcordia SR-332 (Confidential level: 90%, I/P: 115VAC,O/P: 100% load) at Vertical Mounting Orientation 3) All parameters are specified at 25°C ambient unless otherwise noted
STANDARDS & APPROVALS
Electronic Equipment in Power Installations
EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Ex II 3G ATEX 97/9/EC IECEX
(For DRP048V480W1BA) Certificate No. EPS 12 ATEX 1 491 X
Hazardous Location / ATEX (For DRP048V480W1BA)
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (Vertical > +50°C derating)], EN 60079-0:2009, EN 60079-15:2010 [Ex II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C (Vertical > +50°C derating)]
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP048V480W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output: 4.0KVAC Input to Ground: 1.5KVAC Output to Ground: 1.5KVAC
24
Delta DRB-24V020ABBUFFER MODULE DIN RAIL 20 AMP
Features
• Full corrosion resistant Aluminium chassis• Long minimum buffering time of 250ms @ 24V/20A• Can connect in parallel to increase buffering time• Charging time of < 30 seconds• Conformal coating on PCBA to protect against chemical and
dust pollutants• Hazardous Locations approval to ATEX and Class I, Div 2
(DRB-24V020ABA)• IP20 Compliant• Overvoltage / Overcurrent / Short Circuit Protections• Meets worldwide safety requirements• RoHS Directive 2011/65/EU Compliant• Reliable design, with expected life of 10 years
MECHANICAL
Dimensions (LxWxH)
121 x 70 x 120.1mm
Case Cover Aluminium
Weight 0.76kg
Indicators Green LED off: Unit is dischargine of Vin <22VDC Green LED on: Unit is fully charged Green LED blinking slowly (1Hz): Unit is charging Green LED blinking quickly (10Hz): Unit is discharging
Cooling System Convection
Input Terminal M3 x 2 Pins (Rated 300V/30A)
Output Terminal M3 x 5 Pins (Rated 300V/30A)
Input/Output Wire AWG 12-10
Signal Wire AWG 24-10
Mounting Rail Standard TS35 DIN Rail in accordance with EN60715
SpecificationsINPUT
Nominal Voltage 24VDC
Nominal Voltage Range 22.8–28.8VDC
Current Charging mode < 0.6VDC Discharging mode 20A max.
Input Power (Standby) 2.5W Average
Max. Signal Input (Inhibit)
35V / 10mA
Max. Inrush current < 20A
Charging Time < 30 sec
OUTPUT
Nominal Voltage 24VDC typ. (depends on Vin)
Output Voltage Range - Switch=“Fix 22V” - Factory setting Switch=“FixVin-1V”
22–28VDC Buffering starts if terminal voltage falls below 22V Buffering starts if terminal voltage is decreased by > 1V
Max. Voltage 35VDC
Current 20A Max.
Buffering Time 250ms Min @ 24V/20A load 5sec Min @ 24V/1A load
Max. Signal Output 35V / 10mA
Signals Inhibit Signal (I) Ready Signal (R) Buffering Signal (B) Supply Voltage (+Vs)
“Low” - Shuts down Buffer Module “High” = Buffer Module is fully charged or in Standby “High” = Buffer Module is discharging or buffering Common +VS, 35V Max.
PARD (20MHz) < 200m Vpp @ 25°C during buffering mode
Parallel Connection Yes
Series Connection No
Protective Device Transient Voltage Suppressor (TVS) for signals
ENVIRONMENTAL
Operating Temp -25°C to +75°C
Component De-rating Vin=22.8-28.8VDC Max. load -T ambient=50°C -Tj <85% of Tjmax
Humidity 95%RH (Non condensing)
Altitude 2,500m
PROTECTIONS
Overvoltage 32V +10%
Overload / Overcurrent 30A Max
Short Circuit No damage
Reverse Polarity Protection
Yes
STANDARDS & APPROVALS
Electronic Equipment EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
CSA to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 (Class I, Division 2, Group A, B, C, D, T4) EN60079-0:2009, EN60079-15:2010 ( ExII 3G Ex nA nC IIc T4 Gc)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input/Output to ground: 1.5KVAC Signal to ground: 1.5KVAC
25
BUFFERINg TIME
DIMENSIONS
TECHNICAL DATASHEET
CliQ II Buffer Module24V 20A / DRB-24V020AB□
All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (October 2013, Rev. 01)
2
Specifications
Input Ratings / Characteristics
Nominal Input Voltage 24VdcInput Voltage Range 22.8-28.8VdcMaximum Input Voltage 35VdcInput Current Charging Moded < 0.6A
Discharging Moded 20A MaxInput Power (Standby Mode) 2.5W AverageMaximum Signal Input (Inhibit) 35V / 10mAMax Inrush Current < 20ACharging Time < 30sec
Output Ratings / Characteristics
Nominal Output Voltage 24Vdc typ. (depends on Vin)Output Voltage Adjustment Range 22-28Vdc
Switch = “Fix 22V” Buffering starts if terminal voltage falls below 22VFactory Setting, Switch = “Vin-1V” Buffering starts if terminal voltage is decreased by > 1V
Maximum Output Voltage 35VdcOutput Current 20A MaxBuffering Time 250ms Min @ 24V/20A Load,5sec Min @ 24V/1A Load
(Refer to Fig. 1)Maximum Signal Output 35V / 10mA
Signals Inhibit Signal (I) “Low” = Shuts down Buffer ModuleReady Signal (R) “High” = Buffer Module is fully charged or in Standby Mode
Buffering Signal (B) “High” = Buffer Module is discharging or in Buffering Mode
Supply Voltage (+VS) Common +VS, 35V Max
PARD (20MHz) < 200mVpp @ 25°C during Buffering Mode
Parallel Connection YesSeries Connection NoProtective Device Transient Voltage Suppressor (TVS) for signals
Fig.1 Buffering Time (Typical Values at “ Vin – 1V” Mode)
MechanicalBuffering Time (Typical Values at “ Vin – 1V” Mode)
26
Delta DRR-20, DRR-40REDUNDANCY MODULES DIN RAIL 20A & 40A
Features
• RoHS Compliant• Relay alarm indirection• Built-in 2 channel DC OK signal• Conformal coating on PCBA to protect against chemical and
dust pollutants• Class I, Div 2 Hazardous Locations (DRR-20A, DRR-40A)• Ease of wire connection to terminals• Wide Input & Output Range 22-60 Vdc• Full corrosion resistance aluminium chassis even with deep
scratches
TECHNICAL DATASHEET
CliQ II Redundancy Module20A, 40A / DRR-20□, DRR-40□
All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (October 2013, Rev. 01)
1
Highlights & Features– RoHS Compliant– Relay alarm indirection– Built-in 2 channel DC OK signal– Caused by rugged handing– Conformal coating on PCBA to protect against chemical and
dust pollutants– Class I, Div 2 Hazardous Locations (DRR-20A, DRR-40A)– Ease of wire connection to terminals– Wide Input & Output Range 22-60 Vdc– Full corrosion resistance aluminium chassis even with deep
scratches
Safety Standards
CB Certified for worldwide use
Model Number: DRR-20□, DRR-40□Unit Weight: 0.37kg, 0.51 kgDimensions (L x W x D): 121 x 50 x 122.1 mm
General Description
The new Redundancy Module DRR 20□ and DRR 40□ are the latest offering from one of the World’s No.1 Power Supply Company. The product offers a variable input & output voltage from 22-60V, a wide temperature range from -40°C to 80°C. The state-of-the-art design is made to withstand harsh industrial environments. The rugged, compact aluminium case is shock and vibration resistant according to IEC60068-2-6. Due to the wide input & output voltage range from 22 to 60Vdc, the Delta’s CliQ II Redundancy Module is able to support power supply in parallel operation. The DRR module has an alarm relay contact as an indicator.
Model Information
CliQ II Redundancy Modules
Model Number Input Voltage Range Output Voltage Output CurrentDRR-20□ 24-48Vdc Vin-0.65V (Typ) 20A
DRR-40□ 40A
Model Numbering
DR R - □XXDIN Rail Redundancy Module Output Current
20 – 20A40 – 40A
A - Metal Case, with Class I, Div 2N - Metal Case, without Class I, Div 2
MECHANICAL
Dimensions (LxWxH) 121 x 50 x 122.1mm
Case Cover Aluminium
Weight 0.375kg 0.515kg
Indicators DC Input OK: Vin1 OK and Vin2 OK (Green LED)
STANDARDS & APPROVALS
Electrical Equipment IEC60204-1 (Over Voltage Category III)
Electrical Safety UR/cUR recognized to UL60950-1, SIQ BG to EN60950-1, CB test certificate and report to IEC60950-1 and CE.
Industrial Control Equipment
UL/cUL recognize to UL508
Hazardous Location / ATEX
cCSAus to CSA C22.2 No.213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A,B,C,D T4, Ta = -40°C to +80°C (> +50°C derating)] EN60079-0:2009, EN60079-15:2010 [ExII 3G Ex nA nC IIC T4 Gc, Ta = -40°C to +80°C (> +50°C derating)]
CE Conformance with EMC guideline 2004/108/EC and for low voltage guideline 2006/95/EC For DRR-20A and DRR-40A: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Electronic equipment
EN50178 / IEC62103
Safety Entry Low Voltage
PELV (EN60204), SELV (EN60950)
RoHS Compliant RoHS Directive 2011/65/EU Compliant
Protection Against Electric Shock
DIN 57100-410
SpecificationsINPUT DRR-20 DRR-40
Nominal Voltage 24-48VDC 24-48VDC
Current 20A max. 40A max.
Input Voltage Alarm / Relay Contacts
24V system: both Vin1 & Vin2 >18V ± 5% or <30V max. relay contacts
48V system: both Vin1 & Vin2 >36V ± 5% or <60V max. relay contacts
Note: The LED will turn on when The Vin1 & Vin2 > 18V ±5% (For 24V system) or > 36V ±5% (For 48V system) and not more than 30V (For 24V system) or not more than 60V (For 48V system), The relay contacts will be closed. If Vin1 & Vin2 is under or over this range, The LED will be turn off.
OUTPUT
Nominal Voltage Vin-0.65V (Typ) Vin-0.65V (Typ)
Nominal Current 20A max. 40A max.
Derating above +50 °C > 50°C (2.5% / K.) > 50°C (2.5% / K.)
Short Circuit / Over Load Limit
<25A <50A
Efficiency > 97% typ. > 97% typ.
Note: The overload condition must be controlled by The PSUs in parallel; The limit of input current would not more than 25A (For 20A module) or not more than 50A (For 60A module).
ENVIRONMENTAL
Operating Temp -40°C to +80°C
Power De-rating > 50% of Full load @ 70°C derated Linearly
Humidity 95%RH (Non condensing)
Continued next page
27
Delta DRR-20, DRR-40REDUNDANCY MODULES DIN RAIL 20A & 40A
DIMENSIONS DRR-40
DIMENSIONS DRR-20
28
Delta DRU-24V40ABNDC-UPS MODULE DIN RAIL 20V 40A
Features
• Full corrosion resistant Aluminium chassis• Suitable for 24V system up to 40A• Built-in diagnostic monitoring for DC OK, Discharge and
Battery Fail by relay contacts• LED indicator for DC OK, Battery Fail, DC Input, Battery
Reverse Polarity and Battery Discharge• High MTBF > 500,000 hrs as per Telcordia SR-332• Wide operation temperature range from -20°C to +60°C• Conformal coating on PCBA to protect against chemical and
dust pollutants
MECHANICAL
Dimensions (LxWxH) 121 x 50 x 117.3mm
Case Cover Aluminium
Weight 0.60kg
Cooling System Convection
Input/Output Terminal 4 Pins (Rated 600V/60A)
Signal 6 Pins (Rated 300V/27A)
Input/Output Wire AWG 12-6 (Load: 0-20A) AWG 8-6 (Load 20-40A)
Signal Wire AWG 24-12
Mounting Rail Standard TS35 DIN Rail in accordance with EN60715
STANDARDS & APPROVALS
Electronic Equipment EN50718 / IEC62103
Electrical Safety SIQ to EN60950-1, UL/cUL recognized to UL60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC60950-1
Industrial Control Equipment
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
CSA to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 (Class I, Division 2, Group A, B, C, D, T4) EN60079-0:2009, EN60079-15:2010 ( ExII 3G Ex nA nC IIc T4 Gc)
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Power Port to Housing 1.0KVac Signal Port to Housing 1.0KVac Power Port to Signal Port 1.0KVac
SpecificationsINPUT
Nominal Voltage 24VDC
Current 2A ± 1A
Efficiency Charging mode: > 70.0% Buffering mode: > 99.0%
Charging Time* < 3hr ± 1hr for battery 24V/15AH
*Charging time depends on the last state of discharge w.r.t. buffering time and load current.
OUTPUT
Output Voltage Range 23–28VDC
Current 40.0A Max.
Power 960W Max (24V, 40A)
Voltage Drop Between Input and Output
Charging mode: 0V between DC input to load Buffering mode: 0.1V between battery to load @ 40A load
BATTERY INPUT/OUTPUT CHARACTERISTICS
Nominal Battery Voltage 24Vdc, SLA Sealed lead acid battery 2 x 12Vdc, SLA Sealed lead acid battery
Battery Voltage Range 23-28Vdc (continuously operating) 30Vdc Max (the maximum voltage that will not cause damage to the unit) 14Vdc Min (the voltage level of battery to enable “BAT Fail” function)
Battery Capacity 7.5AH/ 12AH/ 15AH
Battery Fuse Auto 50A / 80V, FK3 (Littelfuse) or similar in the battery path. The battery fuse protects the wires between the battery and the unit.
Battery Charging Mode CC-mode (constant current) at 2A
End-of-Charge Voltage The unit always charge with fix input voltage value
ENVIRONMENTAL
Operating Temp -20°C to +60°C
De-rating No power de-rating across the entire operating temperature range (-20°C to +60°C)
Humidity 5–95%RH (Non condensing)
Altitude 0–3,000m
PROTECTIONS
Overvoltage 42-52A, Latch-off Mode
Over Temperature < 90°C Surrounding Air Temperature inside the unit, Latch-off Mode
Short Circuit (at system) Shutdown, Latch-off Mode
Input Polarity Protection* Yes (DC OK = open contact), LED Status = Orange)
Battery Polarity Protection**
Yes (DC OK = open contact), LED Status = Orange)
Wrong Battery Voltage Protection
Yes, 30Vdc Max (the maximum voltage that will not cause damage to the unit)
Deep Discharge Protection
Yes (23V ± 0.5V)**
Degree of Protection IP20
Protection Against Shock Class III
Continued next page
*If the orange status LED is on, this indicates a failure in the installation. In this case, do not turn on power supply while the battery is connected. Danger of explosion! ** The unit will stop operating when the battery voltage detected is less than 23V ± 0.5V
29
BUFFERINg TIME VS OUTPUT CURRENT
DIMENSIONS
TECHNICAL DATASHEET
CliQ II DC-UPS Module24V 40A / DRU-24V40ABN
All parameters are specified at 25°C ambient unless otherwise indicated. www.DeltaPSU.com (May 2014, Rev. 00)
3
Buffering Time
Output Current
Buffering Time7.5AH 12AH 15AH
2.5A 6,500s 14,500s 19,000s
5A 3,000s 7,000s 9,000s10A 1,200s 2,400s 3,200s20A 400s 1,100s 1,500s30A 120s 450s 600s40A 25s 200s 280s
Mechanical
Case Cover / Chassis Aluminium
Dimensions (L x W x D) 121 x 50 x 117.3 mm
Unit Weight 0.60 kg
Cooling System Convection
Terminal Input / Output 4 Pins (Rated 600V/60A)
Signal 6 Pins (Rated 300V/27A)
Wire Input / Output AWG 12-6 (Load: 0-20A)AWG 8-6 (Load 20-40A)
Signal AWG 24-12Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715Noise (1 Meter from power supply) Sound Pressure Level (SPL) < 40dBA
Fig. 1 Buffering Time VS. Output Current
30
Delta DRP024V060W3BNAC-DC DIN RAIL 24 VOLT 60 WATTS 3 PhASE
Features
• Universal AC input voltage: 3 x 320VAC – 600VAC (3-Phase) or 2 x 360VAC – 600VAC (2-Phase)
• Power will not de-rate for the entire input voltage range• Power Boost of 150% for 5 seconds• Full corrosion resistant aluminium chassis• Conformal coating on PCBA to protect against chemical and
dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 50 x 117.3mm
Case Cover Aluminium
Weight 0.66kg
Cooling System Convection
Input Terminal 4 Pins (Rated 600V/35A)
Output Terminal 4 Pins (Rated 300V/28A)
Input/Output Wire AWG 18-12
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating Vertical Mounting
> 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 5% / °C
Power De-rating Horiztonal Mounting
> 45°C de-rate power by 2.5% / °C > 65°C de-rate power by 5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 3 x 320-600VAC (3-Phase) or 2 x 360-600VAC (2-Phase)
Current < 0.30A@3 x 400VAC, < 0.25A@ 3 x 500VAC
Frequency 47–63Hz
Efficiency* at 100% load > 86.0% @ 3 x 400VAC & 3 x 500VAC
Max. Inrush current < 30A @ 3 x 400VAC & 3 x 500VAC
Leakage current < 3.5mA @ 3 x 400VAC & 3 x 500VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 2.50A (continuously operating at 24V) 3.75A (Power Boost for 5 seconds at 24V)
Power 60W (continuously operating at 24V) 90W (Power Boost for 5 seconds at 24V
Line regulation < 0.5% typ. (@ 320-600VAC, 100% load)
Load regulation < 1% typ. (@ 320-600VAC, 0–100% load)
PARD (20MHz) < 50mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 1,000ms @ nominal input (100% load)
Hold-up Time > 20ms @ 3 x 400VAC > 40ms @ 3 x 500VAC (100% load)
NOTES: *Fulfills test conditions for up to 600Vac input voltage.
STANDARDS & APPROVALS
Safety SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Electrical Equipment
In Power Installations: EN 50178 / IEC 62103
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC. For DRP024V060W3BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output 4.0KVAC Input to Ground 1.5KVAC Output to Ground 1.5KVAC
31
Delta DRP024V120W3BNAC-DC DIN RAIL 24 VOLT 120 WATTS 3 PhASE
Features
• Universal AC input voltage without power de-rating• High efficiency > 88% @ 230VAC• Power Boost of 150% for 5 seconds• Full corrosion resistant Aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Conformal coating on PCBA to protect against chemical
and dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 50 x 117.3mm
Case Cover Aluminium
Weight 0.66kg
Cooling System Convection
Input Terminal 4 Pins (Rated 600V/35A)
Output Terminal 4 Pins (Rated 300V/28A)
Input/Output Wire AWG 18-12
ENVIRONMENTAL
Operating Temp -25°C to +75°C
Power De-rating Vertical Mounting
> 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 5% / °C
Power De-rating Horiztonal Mounting
> 40°C de-rate power by 2.5% / °C > 60°C de-rate power by 5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 3 x 320-600VAC (3-Phase) or 2 x 360-600VAC (2-Phase)
Current < 0.50A@115VAC, < 0.40A @ 230VAC
Frequency 47–63Hz
Efficiency* at 100% load > 88.0% @ 3 x 400VAC & 3 x 500VAC
Max. Inrush current < 30A @ 3 x 400VAC & 3 x 500VAC
Leakage current < 3.5mA @ 3 x 400VAC & 3 x 500VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 5.00A (continuously operating at 24V) 7.50A (Power Boost for 5 seconds at 24V)
Power 120W (continuously operating at 24V) 180W (Power Boost for 5 seconds at 24V
Line regulation < 0.5% typ. (@ 320-600VAC, 100% load)
Load regulation < 1% typ. (@ 320-600VAC, 0–100% load)
PARD (20MHz) < 50mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 1,000ms @ nominal input (100% load)
Hold-up Time > 20ms @ 3 x 400VAC > 40ms @ 3 x 500VAC (100% load)
NOTES: *Fulfills test conditions for up to 600Vac input voltage.
STANDARDS & APPROVALS
Safety SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Electrical Equipment
In Power Installations: EN 50178 / IEC 62103
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP024V120W3BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output 4.0KVAC Input to Ground 1.5KVAC Output to Ground 1.5KVAC
32
Delta DRP024V240W3BNAC-DC DIN RAIL 24 VOLT 240 WATTS 3 PhASE
Features
• Universal AC input voltage: 3 x 320VAC – 600VAC (3-Phase) or 2 x 360VAC – 600VAC (2-Phase)
• Power will not de-rate for the entire input voltage range• Power Boost of 150% for 5 seconds• Full corrosion resistant aluminium chassis• Conformal coating on PCBA to protect against chemical and
dust pollutants• Hazardous Locations approval to ATEX and Class I, Div 2
MECHANICAL
Dimensions (LxWxH)
121 x70 x 117.3mm
Case Cover Aluminium
Weight 0.89kg
Cooling System Convection
Input Terminal 4 Pins (Rated 600V/35A)
Output Terminal 4 Pins (Rated 300V/28A)
Input Wire Output Wire
AWG 18-12 AWG 16-12
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating Vertical Mounting
> 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 5% / °C
Power De-rating Horiztonal Mounting
> 40°C de-rate power by 2.5% / °C > 60°C de-rate power by 5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 3 x 320-600VAC (3-Phase) or 2 x 360-600VAC (2-Phase)
Current < 0.75A@3 x 400VAC, < 0.65A@ 3 x 500VAC
Frequency 47–63Hz
Efficiency* at 100% load > 92.0% @ 3 x 400VAC & 3 x 500VAC
Max. Inrush current < 40A@ 3 x 400VAC & 3 x 500VAC
Leakage current < 3.5mA @ 500VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 10.0A (continuously operating at 24V) 15.0A (Power Boost for 5 seconds at 24V)
Power 240W (continuously operating at 24V) 360W (Power Boost for 5 seconds at 24V)
Line regulation < 0.5% typ. (@ 320-600VAC, 100% load)
Load regulation < 1% typ. (@ 320-600VAC, 0–100% load)
PARD (20MHz) < 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 1,000ms @ nominal input (100% load)
Hold-up Time > 20ms @ 3 x 400VAC > 40ms @ 3 x 500VAC (100% load)
NOTES: *Fulfills test conditions for up to 600Vac input voltage.
STANDARDS & APPROVALS
Safety SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Electrical Equipment
In Power Installations: EN 50178 / IEC 62103
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP024V120W3BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output 4.0KVAC Input to Ground 2.0KVAC Output to Ground 1.5KVAC
33
Delta DRP024V480W3BNAC-DC DIN RAIL 24 VOLT 480 WATTS 3 PhASE
Features
• Universal AC input voltage: 3 x 320Vac – 600Vac (3-Phase) or 2 x 360Vac – 600Vac (2-Phase)
• Power will not de-rate for the entire input voltage range• Power Boost of 150% for 5 seconds and 200% for 2 seconds• Full corrosion resistant aluminium chassis• Conformal coating on PCBA to protect against chemical and
dust pollutants• Hazardous Locations approval to ATEX and Class I, Div 2
MECHANICAL
Dimensions 121 L x 140 W x 117.3 H mm
Case Cover Aluminium
Weight 1.35kg
Cooling System Convection
Input Terminal 4 Pins (Rated 600V/35A)
Output Terminal 4 Pins (Rated 300V/28A)
Input Wire Output Wire
AWG 18-8 AWG 12-10
ENVIRONMENTAL
Operating Temp -25°C to +80°C
Power De-rating Vertical Mounting
> 50°C de-rate power by 2.5% / °C > 70°C de-rate power by 5% / °C
Power De-rating Horiztonal Mounting
> 40°C de-rate power by 2.5% / °C > 60°C de-rate power by 5% / °C
Humidity < 95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage Range 3 x 320-600VAC (3-Phase) or 2 x 360-600VAC (2-Phase)
Current < 1.00A@ 3 x 400VAC, < 0.75A@ 3 x 500VAC
Frequency 47–63Hz
Efficiency* at 100% load > 91.0% @ 3 x 400VAC & 3 x 500VAC
Power Factor > 0.95 3 x 400VAC, > 0.94 3 x 500VAC
Max. Inrush current < 50A @ 3 x 400VAC & 3 x 500VAC
Leakage current < 3.5mA @ 500VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 20.0A (continuously operating at 24V) 30.0A (Power Boost for 5 seconds at 24V) 40.0A (Power Boost for 2 seconds at 24V)
Power 480W (continuously operating at 24V) 720W (Power Boost for 5 seconds at 24V) 960W (Power Boost for 2 seconds at 24V)
Line regulation < 0.5% typ. (@ 3 x 320-600VAC input, 100% load)
Load regulation < 1% typ. (@ 3 x 320-600VAC input, 0–100% load)
PARD (20MHz) < 150mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 1,000ms @ nominal input (100% load)
Hold-up Time > 20ms @ 3 x 400Vac & 3 x 500Vac (100% load)
NOTES: *Fulfills test conditions for up to 600Vac input voltage.
STANDARDS & APPROVALS
Safety SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Electrical Equipment In Power Installations: EN 50178 / IEC 62103
Hazardous Location / ATEX
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta = -25°C to +80°C (> +50°C derating)] EN 60079-0:2012, EN 60079-15:2010 [ II 3G Ex nA IIC T4 Gc, Ta= -25°C to +80°C (> +50°C derating)]
Ex II 3G ATEX 94/9/EC
Certificate No. EPS 13 ATEX 1 575 X
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC For DRP024V120W3BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 94/9/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output 4.0KVAC Input to Ground 2.0KVAC Output to Ground 1.5KVAC
34
Delta DRP024V960W3BNAC-DC DIN RAIL 24 VOLT 960 WATTS 3 PhASE
Features
• Universal AC input voltage: 3 x 320VAC – 600VAC (3-Phase) or 2 x 360VAC – 600VAC (2-Phase)
• Power Boost of 150% for 5 seconds• Full corrosion resistant aluminium chassis• Conforms to harmonic current IEC/EN 61000-3-2, Class A• Conformal coating on PCBA to protect against chemical and
dust pollutants
MECHANICAL
Dimensions (LxWxH)
121 x 255 x 117.3mm
Case Cover Aluminium
Weight 2.60kg
Cooling System Convection
Input Terminal 4 Pins (Rated 600V/35A)
Output Terminal 4 Pins (Rated 300V/30A)
Input Wire Output Wire
AWG 18-8 AWG 12-10
ENVIRONMENTAL
Operating Temp -25°C to +65°C
Power De-rating Vertical Mounting
> 50°C de-rate power by 2.5% / °C
Humidity 5–95%RH (Non condensing)
Altitude 0–2,000m
SpecificationsINPUT
Voltage 3 x 320-600VAC (3-Phase) or 2 x 380-600VAC (2-Phase)
Current < 1.70A@3 x 400VAC, < 1.40A@ 3 x 500VAC
Frequency 47–63Hz
Efficiency* at 100% load > 92.0% @ 3 x 400VAC & 3 x 500VAC
Power Factor at 100% load
> 0.95 @ 3 x 400VAC, > 0.94 @ 3 x 500VAC
Max. Inrush current < 40A@ 3 x 400VAC & 3 x 500VAC
Leakage current < 3.5mA @ 3 x 600VAC
OUTPUT
Voltage 24V
Output Voltage Range 24–28V
Current 40.0A (continuously operating at 24V) 60.0A (Power Boost for 5 seconds at 24V)
Power 960W (continuously operating at 24V) 1440W (Power Boost for 5 seconds at 24V)
Line regulation < 0.5% typ. (@ 3 x 320-600VAC, 100% load)
Load regulation < 1% typ. (@ 3 x 320-600VAC, 0–100% load)
PARD (20MHz) < 240mVpp
Rise Time < 100ms @ nominal input (100% load)
Start-up Time < 1,500ms @ nominal input (100% load)
Hold-up Time > 20ms @ 3 x 400VAC & 3 x 500VAC (100% load)
NOTES: *Fulfills test conditions for up to 600Vac input voltage.
STANDARDS & APPROVALS
Safety SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Electrical Equipment
In Power Installations: EN 50178 / IEC 62103
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Materials & Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output 4.0KVAC Input to Ground 2.0KVAC Output to Ground 1.5KVAC
35
Notes:
POWERBOX AUSTRALIA PTY LTDSydney Head Office:4 Beaumont Road, Mt Kuring-gai, NSW 2080Melbourne:2/896 Burwood highway, Ferntree gully VIC 3156
Toll Free: 1800 251 380 Email: sales@powerbox.com.au
POWERBOX PACIFIC LTDNew Zealand 1a henry Rose Place, Albany Auckland New Zealand 0632
Toll Free: 0800 104 480 Email: sales@powerbox.co.nz
www.powerbox.com.auwww.powerbox.co.nz
14PB014 Delta DIN Rail Brochure Sep 2014